Magellan MG-6060 用户手册

下载
页码 48
Paradox Magellan Systems
 
23
presence and functionality. If a device has not sent a signal 
within the specified time period, Magellan can generate a 
trouble, an alarm and/or transmit a report code to the central 
monitoring station as defined by the Wireless Transmitter 
Supervision Options (page 22). Sections [103] and [104] 
determine which zones will be supervised and which will not. 
Enable the option pertaining to the zone you wish Magellan to 
supervise.
Check-in Supervision Time
Section [096]: Option [7]
Option [7] OFF =Check-in supervision time = 24Hrs (default)
Option [7] ON =Check-in supervision time = 80 minutes
Section [096] option [7] defines the time period that Magellan will 
expect a check-in status signal from the specified wireless 
transmitters as defined in the Check-in Supervision Options 
(page 22). If no signal is received within the check-in supervision 
time, Magellan’s reaction will be defined by the Wireless 
Transmitter Supervision Options (page 22).
Panic Alarms
Section [091]: Options [1], [2] and [3]
Option [1] OFF = Panic 1 (Emergency Panic) disabled (default)
Option [1] ON =
Panic 1 (Emergency Panic) enabled
Option [2] OFF = Panic 2 (Auxiliary Panic) disabled (default)
Option [2] ON =
Panic 2 (Auxiliary Panic) enabled
Option [3] OFF = Panic 3 (Fire Panic) disabled (default)
Option [3] ON =
Panic 3 (Fire Panic) enabled
Enable section [091] options [1], [2] and [3] to enable the 
system’s three Panic alarms. Each panic alarm is activated by 
pressing two keys simultaneously and holding them down for 2 
seconds. See Table 7 on page 23 for the appropriate panic 
alarm keys. Whether these panic alarms will generate a silent or 
audible alarm is determined by section [091] options [4] to [6] 
(see Panic Alarm Types on page 23).
Table 7: Panic Alarm Keys
Remote controls can also be programmed to generate panic 
alarms. See Programming the Remote Control’s Buttons on 
page 18 for more information on programming remote controls 
to generate panic alarms.
Panic Alarm Types
Section [091]: Options [4], [5] and [6]
Option [4] OFF =Panic 1 (Emergency Panic) is silent (default)
Option [4] ON =Panic 1 (Emergency Panic) is audible
Option [5] OFF =Panic 2 (Auxiliary Panic) is silent (default)
Option [5] ON =Panic 2 (Auxiliary Panic) is audible
Option [6] OFF =Panic 3 (Fire Panic) is silent (default)
Option [6] ON =Panic 3 (Fire Panic) is pulsed 
Options [4] to [6] represent the alarm types of panic alarms 1 to 3 
respectively.
Silent Alarm: The Magellan console will emit a confirmation beep 
and transmit the appropriate Panic report code (if programmed in 
section [139]). The console will not enable its speaker or the 
system siren.
Audible Alarm: Same as the silent alarm except that the console 
will enable its speaker and system siren until a user cancels the 
alarm (disarms) with a valid access code or when the Bell Cut-off 
timer elapses (if enabled; see Bell Cut-off Timer on page 22).
Pulsed Alarm (Fire Panic only): Same as the audible alarm 
except that the siren will be pulsed as shown in Figure 17 on 
page 14. Refer to Standard 24Hr. Fire Zones on page 14 for 
more information on a pulsed siren output.
Keys to press
Panic Alarm Type
[1] and [3]
Panic 1 (Emergency Panic)
[4] and [6]
Panic 2 (Auxiliary Panic)
[7] and [9]
Panic 3 (Fire Panic)