REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
UNIT HEIGHT
(in./mm)
lb
kg
A
B
C
D
E
48SS018040
208/230-1-60
296
135
87/40
68/31
82/37
59/27
27.4/697
48SS024040
208/230-1-60
327
149
103/47
49/22
129/59
46/21
27.4/697
48SS024060
208/230-1-60
339
155
106/48
52/24
132/60
49/22
27.4/697
48SS030040
208/230-1-60, 208/230-3-60
344
157
106/48
53/24
132/60
53/24
27.4/697
48SS030060/080
208/230-1-60, 208/230-3-60
356
162
102/46
71/32
123/56
60/27
27.4/697
48SS036060/080
208/230-1-60, 208/230-3-60, 460-3-60
360
164
92/42
82/37
117/53
69/31
27.4/697
48SS036100/120
208/230-1-60, 208/230-3-60, 460-3-60
372
169
95/43
85/39
120/55
72/33
27.4/697
48SS042060/080
208/230-1-60, 208/230-3-60, 460-3-60
399
181
101/46
92/42
125/57
81/37
31.4/798
48SS042100/120
208/230-1-60, 208/230-3-60, 460-3-60
411
187
104/47
95/43
128/58
84/38
31.4/798
UNIT
F
in./mm
G
in./mm
CENTER OF GRAVITY in./mm
X
Y
Z
48SS018040
19
7
8
/504.8
22
1
4
/565.4
25.04/636
22.72/577
13.16/334.3
48SS024040
26.90/683.3
20.17/512.3
48SS024060
26.82/681.2
20.22/513.6
48SS030040
26.57/674.9
20.1 /509.3
48SS030060/080
26.93/684
21.1 /535.4
48SS036060/080
27.31/693.7
21.0 /532.6
48SS036100/120
27.23/691.6
21.0 /533.1
48SS042060/080
23
7
8
/606.4
26
1
4
/666.8
26.87/682.5
21.0 /533.1
14.96/380
48SS042100/120
26.81/681
21.0 /533.7
LEGEND
CG
— Center of Gravity
COND — Condenser
LV
— Low Voltage
MAT’L
— Material
NEC
— National Electrical Code
REQ’D — Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
Fig. 3 — 48SS018-042 With Optional Base Rail, Unit Dimensions
3