Carrier 48SX024-060 用户手册

下载
页码 52
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb
kg
A
B
C
D
48SS048080
208/230-1-60, 208/230-3-60, 460-3-60
414
188
107/49
83/38
158/72
66/30
48SS048100/120/140
208/230-1-60, 208/230-3-60, 460-3-60
426
193
110/50
86/39
159/72
71/32
48SS060080
208/230-1-60, 208/230-3-60, 460-3-60
453
206
117/53
93/42
167/76
76/35
48SS060100/120/140
208/230-1-60, 208/230-3-60, 460-3-60
465
211
120/55
96/44
167/76
82/37
UNIT
CENTER OF GRAVITY (in./mm)
X
Y
Z
48SS048080
28.76/731
23.46/596
15.35/390
48SS048100/120/140
28.42/722
23.42/595
15.35/390
48SS060080
28.36/720
23.27/591
15.35/390
48SS060100/120/140
27.95/710
23.23/590
15.35/390
LEGEND
CG
— Center of Gravity
COND — Condenser
LV
— Low Voltage
MAT’L
— Material
NEC
— National Electrical Code
REQ’D — Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
Fig. 4 — 48SS048,060 Without Base Rail, Unit Dimensions
4