Regency L676 用户手册

下载
页码 56
Regency
®
 L676 Direct Vent Gas Fireplace
26
INST
ALLA
TION
IN
OUT
1
3
5
6
4
2
GAS PIPE PRESSURE 
TESTING
The appliance must be isolated from the gas 
supply piping system by closing its individual 
manual shut-off valve during any pressure 
testing of the gas supply piping system at 
test pressures equal to or less than 1/2 psig. 
(3.45 kPa).  Disconnect piping from valve at 
pressures over 1/2 psig.
The manifold pressure is controlled by a regulator 
built into the gas control, and should be checked 
at the pressure test point.
Note: To properly check gas pressure, both 
inlet and manifold pressures should 
be checked using the valve pressure 
ports on the valve.
1)  Make sure the valve is in the "OFF" 
position.
2)  Loosen the "IN" and/or "OUT" pressure 
tap(s), turning counterclockwise with a 
 
1/8" wide fl at screwdriver.
3)  Attach manometer to "IN" and/or "OUT" 
pressure tap(s) using a 5/16" ID hose.
4)  Light the pilot and turn the valve to "ON" 
position.
5)  The pressure check should be carried out 
with the unit burning and the setting should 
be within the limits specifi ed on the safety 
label.
6)  When fi nished reading manometer, turn 
off the gas valve, disconnect the hose and 
tighten the screw (clockwise) with a 1/8" fl at 
screwdriver. Note: Screw should be snug, 
but do not over tighten.
SIT 825 VALVE DESCRIPTION
1)  Gas on/off knob
2) Electronically 
Operated 
Hi/Lo
3) Pilot 
Adjustment
4) Thermocouple 
Connection 
option
5)  Outlet Pressure Tap
6) Inlet 
Pressure 
Tap
7) Pilot 
Outlet
8)  Main Gas Outlet
9) Alternative 
TC 
Connection 
Point
Important: Always check for gas leaks with a 
soap and water solution or gas leak detector. 
Do not use open fl ame for leak testing.
HIGH ELEVATION
This unit is approved in Canada for altitude 0 
to 4500 ft. (CAN1 2.17-M91).
GAS LINE 
INSTALLATION
Since some municipalities have additional 
local codes it is always best to consult with 
your local authorities and the CAN/CGA B149 
installation code.
For USA installations follow local codes and/or 
the current National Fuel Gas Code, ANSI 
Z223.1.
When using copper or fl ex connectors use only 
approved fi ttings. Always provide a union so 
that gas lines can be easily disconnected for 
servicing. Flare nuts for copper lines and fl ex 
connectors are usually considered to meet this 
requirement.
Periodically check the pilot fl ames. Correct 
fl ame pattern has three strong blue fl ames: 
1 fl owing around the thermopile, 1 around 
the thermocouple and 1 fl owing across the 
burner (it does not have to be touching the 
burner).
Note:  If you have an incorrect fl ame pattern, 
contact your Regency
®
 dealer for 
further instructions.
Incorrect fl ame pattern will have small, 
probably yellow fl ames, not coming into 
proper contact with the rear burner or 
thermopile or thermocouple. 
 
PILOT ADJUSTMENT
L676-NG SYSTEM DATA
Min. Supply Pressure
5" WC (1.25 kpa)
Low Setting Man. 
Pressure
1.6" WC (0.39 kpa)
Max. Manifold 
Pressure
3.5" WC (0.87 kpa)
Orifi ce Size (Front 
Burner)
#48 DMS
Orifi ce Size (Back 
Burner)
#34 DMS
Minimum Input
11,000 Btu/h 
(3.22 kW)
Maximum Input
42,000 Btu/h
(12.3 kW)
L676-LP SYSTEM DATA
Min. Supply Pressure
12" WC (2.98 kpa)
Low Setting Man. 
Pressure
3.6" WC (2.49 kpa)
Max. Manifold 
Pressure
10" WC (2.98 kpa)
Orifi ce Size (Front 
Burner)
#56 DMS
Orifi ce Size (Back 
Burner)
#53 DMS
Minimum Input
9,000 Btu/h 
(2.64 kW)
Maxiumm Input
40,000 Btu/h
(11.72 kW)
INSTALLATION