TIC-LF470B   
Field Intelligent Device Series 
Electromagnetic Flowmeter 
LF470/LF612 
1/10",1/6”,1/4" (2.5,4,6mm )
 
Introduction
 
The electromagnetic flowmeter uses Faraday’s Law of 
electromagnetic induction to measure the process flow. 
The device consists of two units: a detector, through 
which
 
the
 
fluid
 
to
 
be
 
measured
 
flows
 
and
 
in
 
which
 
low-level signals proportional to flow rates are obtained; 
and a converter, which supplies excitation current to the
 
detector,
 
and
 
amplifies
 
the
 
signals
 
from
 
the
 
detector and
 
then
 
processes
 
and
 
converts
 
the
 
signals
 
into
 
the
 
4–20
 
mA
 
dc current
 
signal. The LF470 is a small meter size 
detector designed to measure a small amount of fluids 
containing substances such as chemicals. 
The wetted materials for the LF470 are corrosion 
resistant ceramic and platinum electrods and are 
applicable to almost any kind of fluids. The LF470 is a 
lightweight palm-sized detector.Combined with 
multi-functional converter LF612 (separate type) and 
LF232*
1
 (separate type) equipped with its patented 
Noise-Sentry original noise-suppression circuit and 
advanced algorithms. The LF470 is highly resistant to 
noise and provides a stable output even for fluids 
containing slurries. IR (Infrared) switches enable 
parameter setting of the converter without removing the 
cover. Flow direction can be set in either way, and its 
unique 128 x 128 dot matrix LCD    display allows the 
LCD to be rotated electronically to be rotated to 90, 180 
and 270 degrees without opening the cover 
The AF900 hand-held terminal (HART*
communicator) 
can be used to communicate with the flowmeter from a 
remote place. PROFIBUS-PA*
  interface is available 
as an option. 
*1: Please refer to the document ”TIC-LF232”. 
*2: HART protocol (Highway Addressable Remote 
Transducer) is a communication protocol for industrial 
sensors recommended by the HCF
 
(HART
 
Communication
 
Foundation). 
*3: PROFIBUS is the communication protocol for factory   
and process automation that the PROFIBUS Organization 
recommends. Instead of analog control with a 
conventional analog signal (4-20mA), it is the fieldbus 
which digitizes all signals. Flowmeters support 
PROFIBUS-PA. 
 
 
 
 
 
 
 
 
 
 
 
Figure 2.  Electromagnetic Flowmeter 
LF470/LF612 
 
 
 
 
Specifications
 
 
Overall Specifications 
Measurement range in terms of flow velocity: 
0–1.0ft/s to 0–32.8ft/s (0–0.3 m/s to 0–10 m/s ) 
Accuracy: The overall accuracy combined with the 
LF612 or LF232 converter is shown in the 
following table. 
Accuracy 
Flow rate as a 
percent of range
1.0-3.3ft/s  
(0.3-1.0m/s ) 
3.3-32.8ft/s  
(1.0-10m/s ) 
50∼100% 
±0.8% of FS 
±0.8% of rate
0∼50% 
±0.8% of FS 
±0.4% of FS 
Note: The accuracy is measured under standard 
operating conditions at Toshiba's calibration facility. 
Fluid conductivity: 50µS/cm minimum 
Fluid temperature: 
Pipe connection material Fluid 
temperature
Stainless steel and other metals 
14 to 248 °F 
(−10℃∼+120℃) 
Polyvinyl chloride 
(shock-resistant) 
14 to 140 °F 
(−10℃∼+60℃) 
Ambient temperature: 14
 
to
 
140
 
°F (–10 to +60
 
°C
 
Structure: IP67 
Power consumption: 
  ・
When combined with the LF612 converter: 
       approximately 12W (20VA) 
    ・When combined with the LF232 converter: 
       approximately 14W (25VA) 
Fluid to be
measured 
Signal cable 
Excitation cable 
Power supply 
4-20mA dc output
and pulse output 
Figure 1. Configuration Diagram 
LF470 
LF612 
Certification number
 
Z01207
 
LF612 or LF232  
Converter
 
LF470 
Detector