Initial Installation
G
AS
 L
INE
 C
ONNECTION
 
AND
 T
ESTING
:
WARNING:  Only  persons  licensed  to  work  with  gas  piping  may  make  the  necessary  gas  connections  to  this 
appliance.  
GAS LINE CONNECTION
•  This stove is equipped with a certified flexible pipe located on the right side of the unit terminating in a 3⁄8” male 
NPT fitting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in Canada, or 
in the USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI 
Z223.1.
•  The  efficiency  rating  of  this  appliance  is  a  product  thermal  efficiency  rating  determined  under  continuous 
operating conditions and was determined independently of any installed system.
The appliance and its shutoff valves must be disconnected 
from the gas supply piping system during any pressure 
testing where the pressure exceeds 1⁄2 PSIG (3.45 KPa) 
or damage will occur to the valve.
The  appliance  must  be  isolated  from  the  gas  supply 
piping  system  by  closing  its  individual  manual  shutoff 
valve  during  any  pressure  testing  of  the  gas  supply 
piping system at test pressures equal to or less than 1⁄2 
psig (3.45 KPa).
Always  check  for  gas  leaks  with  a  soap 
and  water  solution  after  completing  the 
required pressure test.
TO TEST VALVE PRESSURES
The pressure taps are located on the left side of the valve 
• Turn set screw 1 turn counter clockwise to loosen, 
• Place 
5
/
16
” (8 mm) I.D. hose over pressure tap system. 
• Check pressures using a manometer.
• When finished, release pressure, remove hose & tighten setscrew.
Natural Gas
Propane
Front Burner
#48 DMS 
#55 DMS
Rear Burner
#43 DMS
#54 DMS
Manifold Pressure
3.8” W.C. (0.95 KPa)
11.0” W.C. (2.7KPa)
Min. Manifold Pressure
1.1” W.C. (0.27KPa)
2.7” W.C. (0.67KPa)
Max Supply Pressure
7.0” W.C. (1.74KPa)
12.0” W.C. (2.98KPa)
Min. Supply Pressure
5.0” W.C. (1.24KPa)
11.5” W.C. (2.86KPa)
Max BTU/hr Input
38,000 BTU/hr (11.1KW)
38,000 BTU/hr (7.76KW)
Min. BTU/hr Input
20,000 BTU/hr (5.9 KW)
20,000 BTU/hr (5.9KW)
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
O
L I
T
P
TP
TH
TP
TH
IN
OU
T
H
I
LO
N
OF
O
F
LI
P
T O
��������
�������� ���
�����
�������� ���
������
����
����� ����������
�����
��� �������
����
Figure 10: Fully Labeled Gas Valve.
Table 4: Pressure and BTU Information.
12