Operating Instructions
P
ILOT
 L
IGHT
:
1. Turn off the gas to the fireplace.  If not recently done, remove the glass and let the unit air out 
for at least five (5) minutes to clear out any gas. Turn on gas to the heater. Leak test all joints 
with soapy water. NEVER USE AN OPEN FLAME FOR LEAK TESTING. 
����������
������������
Figure 3.  Pilot flame.
2. Start the pilot by pressing the gas control knob and turning it to PILOT.  
While  holding  the  gas  control  knob  in,  press  the  piezo  ignitor  several 
times until the pilot light starts. Hold the gas control knob in for thirty 
(30) seconds. Check that the pilot has fully engulfed the thermocouple 
assembly (see Figure 3).
3. Start the main burner by turning the gas control knob to ON and then turn 
the rocker switch to ON. Check that all burner ports have flame.
4. Leak test all gas joints again.
V
ENTURI
 A
DJUSTMENT
:
 
The venturi adjustment lever is centered above the control panel.
The venturi allows the amount of air coming into the fireplace to be adjusted in order to accommodate 
different climates and venting arrangements. Start the pilot and then the burner. Make sure the pilot 
flame is burning normally and none of the burner ports are plugged. Let the fireplace burn for roughly 
fifteen (15) minutes and then examine the flames.
The  ideal  flame  will  be  blue  at  the  base  and 
light orange above (see Figure 42). The flames 
should be of medium height.  If the flames look 
like  this,  no  venturi  adjustment  is  needed.  If 
the flames are fairly short and mostly blue, the 
fireplace is getting too much air. Therefore, the 
air  shutter  should  be  closed  (push  in)  slightly 
until  the  correct  flames  are  achieved.    Flames 
that are very orange, with tall dark stringy tips 
are not getting enough air.  Open (pull out) the 
venturi until the flames clean up.  If the venturi is 
opened,  then closed all the way, and the correct 
flames cannot be attained, turn off the gas and 
contact the dealer.
Figure 4.  Venturi Adjustment Lever
Warning: Incorrect venturi adjustment may lead to improper combustion, which is a safety hazard. 
Contact the dealer if there is any concern about the venturi adjustment.
NEVER USE AN OPEN FLAME FOR LEAK TESTING
7