Water vapor is a by-product of gas combustion.  An unvented room 
heater produces approximately one (1) ounce (30ml) of water for 
every 1,000 BTU's (.3KW's) of gas input per hour. . 
Unvented room heaters are recommended as supplemental heat (a 
room) rather than a primary heat source (an entire house). In most 
supplemental heat applications, the water vapor does not create a 
problem. In most applications, the water vapor enhances the low 
humidity atmosphere experienced during cold weather. 
The  following  steps  will  help  insure  that  water  vapor  does  not 
become a problem.  
1.  Be sure the heater is sized properly for the application, including 
ample combustion air and circulation air.
2.  If high humidity is experienced, a dehumidifier may be used to 
help lower the water vapor content of the air.
3.  Do  not  use  an  unvented  room  heater  as  the  primary  heat 
source.
This heater shall not be installed in a confined space or unusually 
tight  construction  unless  provisions  are  provided  for  adequate 
combustion and ventilation air.
The National Fuel Gas Code defines a confined space as a space 
whose volume is less than 50 cubic feet per 1,000 Btu per hour 
(4.8m
3
  per  kw)  of  the  aggregate  input  rating  of  all  appliances 
installed in that space and an unconfined space as a space whose 
volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m
3
 
per kw) of the aggregate input rating of all appliances installed in 
that space. Rooms communicating directly with the space in which 
the appliances are installed, through openings not furnished with 
doors, are considered a part of the unconfined space.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough 
fresh air for combustion and ventilation. However, in buildings of 
unusually  tight  construction,  you  must  provide  additional  fresh 
air.
  Unusually  tight  construction  is  defined  as  construction 
where:
a.  Walls and ceilings exposed to the outside atmosphere have 
a continuous water vapor retarder with a rating of one perm 
or less with openings gasketed or sealed, and
b.  Weatherstripping has been added on openable windows and 
doors, and
c.  Caulking  or  sealants  are  applied  to  areas  such  as  joints 
around window and door frames, between sole plates and 
floors, between wall-ceiling joints, between wall panels, at 
penetrations for plumbing, electrical, and gas lines, and at 
other openings.
  If your home meets all of the three criteria above, you must provide 
additional fresh air. See “Ventilation Air From Outdoors,” 
page 7.
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined 
space.   
 
Space: Includes the room in which you will install heater plus any 
adjoining rooms with doorless passageways or ventilation grills 
between the rooms.
1. Determine the volume of the space (length x width x height).
  Length x Width x Height = 
 cu. ft. (volume of 
space)
Example: Space size 16 ft. (length) x 10 ft. (width) x 8 ft. (ceiling 
height) = 1,280 cu. ft. (volume of space)
  If additional ventilation to adjoining room is supplied with grills 
or openings, add the volume of these rooms to the total volume 
of the space.
2.  Divide  the  space  volume  by  50  cubic  feet  to  determine  the 
maximum BTU/Hr the space can support.
 
 (volume of space) ÷ 50 cu. ft. = (maximum 
BTU/Hr the space can support)
Example: 1,280 cu. ft. (volume of space) ÷ 50 cu. ft. = 25.6 or 
25,600 (maximum BTU/Hr the space can support)
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
SPECIFICATIONS
Model
VF24FP3-1
VF24FP2-1
Input    Maximum
20,000
20,000/10,000
            Minimum
14,000
7,000/7,000
Fireplace Dimensions
Height
26 3/8"
26 3/8"
Depth
10 7/8"
10 7/8"
Front Width
22 5/8"
22 5/8"
Rear Width
17 1/4"
17 1/4"
Gas Inlet
3/8"
3/8"
Accessories
VFS-BK
Automatic Blower
EHL-24-1
Brick Liner
VPP1A-22
Aged Brick Liner
VPF24BR
Brass Trim Kit
VPF24SS
Stainless Steel Trim Kit
VPF24HP
Hammered Pewter Trim Kit
Accessories for VF24FP3-1 Only
FRBC-1
Battery Operated Remote Control
FRBTC-1
Battery Operated Remote Control w/Thermostat
FREC-1
Electric Remote Control
FWS-1
Wall Switch
TMV
Wall Thermostat, Millivolt - Reed Switch
TRW
Wireless Remote Wall Thermostat