Empire Comfort Systems VF24FP3-1 用户手册

下载
页码 28
Page 7
20248-2-0806
Figure 1
WARNING:  Rework worksheet, adding the space of the 
adjoining unconfined space. The combined spaces must have 
enough fresh air to supply all appliances in both spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must 
provide two permanent openings: one within 12" of the ceiling 
and one with 12" of the floor. Connect these items directly to the 
outdoors  or  spaces  open  to  the  outdoors. These  spaces  include 
attics and crawl spaces. In most cases for direct communication 
with the outdoors or direct communication through a vertical duct 
a free area opening of one square inch per 4,000 BTU/HR of heater 
input rating for each grill. If a horizontal duct is used, a grill free 
area or duct opening shall have a free area opening of one square 
inch per 2,000 BTU/HR for each grill. Follow the National Fuel 
Code NFPA 54/ANSI Z223.1, Section 5.3 Air for Combustion and 
Ventilation for required size of ventilation grills or ducts.
IMPORTANT:  Do  not  provide openings  for  inlet or  outlet air 
into attic if attic has a thermostat-controlled power vent. Heated 
air entering the attic will activate the power vent.
Figure 2
3.  Add the BTU/Hr of all fuel burning appliances in the space.
 Vent-free heater    
 BTU/Hr
 Gas water heater   
 BTU/Hr
 Gas furnace 
 
 BTU/Hr
 Vented gas heater  
 BTU/Hr
 Gas fireplace logs  
 BTU/Hr
 Other gas appliances*  +   
 BTU/Hr
 Total 
 
 BTU/Hr
Example:  Vented gas heater   
20,000 
BTU/Hr
  
  Vent-free heater  
18,000 
BTU/Hr
  
  Total 
 
38,000 
BTU/Hr
*Do not include direct-vent gas appliances. Direct vent draws 
combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum BTU/Hr the space can support with the 
actual amount of BTU/Hr used.
 
 BTU/Hr (maximum the space can support)
 
 BTU/Hr (actual amount of BTU/Hr used)
  Example: 
    25,600 
BTU/Hr (maximum the space can support)
    38,000 
BTU/Hr (actual amount of BTU/Hr used)
Warning: If the area in which the heater may be operated is smaller 
than that defined as an unconfined space or if the building is of 
unusually  tight  construction,  provide  adequate  combustion  and 
ventilation air by one of the methods described in the National Fuel 
Gas Code, ANSI Z223.1, Section 5.3 or applicable local codes.
The space in the above example is a confined space because the 
actual BTU/Hr used is more than the maximum BTU/HR the space 
can support. You must provide additional fresh air. Your options 
are as follows:
A.  Rework worksheet, adding the space of an adjoining room. If 
the extra space provides an unconfined space, remove door to 
adjoining room or add ventilation grills between rooms. See 
Ventilation Air From Inside Building. 
B.  Vent room directly to the outdoors. See Ventilation Air From 
Outdoors.
C.  Install a lower BTU/Hr heater, if lower BTU/Hr size makes 
room unconfined.
If the actual BTU/Hr used is less than the maximum BTU/Hr the 
space can support, the space is an unconfined space. You will need 
no additional fresh air ventilation.
WARNING: You must provide additional ventilation air 
in a confined space.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. 
When  ventilating  to  an  adjoining  unconfined  space,  you  must 
provide two permanent openings: one within 12" of the ceiling 
and one within 12" of the floor on the wall connecting the two 
spaces (see options 1 and 2, Figure 1). You can also remove door 
into adjoining room (see option 3, Figure 1). Each ventilation grill 
or opening shall have a minimum free area of one square inch per 
1,000 BTU/HR of the total input rating of the gas equipment in 
the confined space.