HEARTH ExTENSION
A hearth extension projecting a minimum of 20" 
in front of and a minimum of 12" beyond each 
side of the fireplace opening is required to protect 
combustible floor construction in front of the fire-
place. Fabricate a hearth extension using a material 
which meets the following specifications: a layer 
of noncombustible, inorganic material having a 
thermal conductivity of K=0.84 BTU IN/FT, HR. 
F (or less) at 1" thick. For example, if the material 
selected has a K factor of 0.25, such as glass fiber, 
the following formula would apply:
 
0.25 x 1.0" = 0.30" thickness required
 
0.84
Thermal conductivity "K" of materials can be 
obtained from the manufacturer or supplier of the 
noncombustible material. If the hearth extension 
is to be covered, use noncombustible material such 
as tile, slate, brick, concrete, metal, glass, marble, 
stone, etc. Provide a means to prevent the hearth 
extension from shifting and seal gap between the 
fireplace frame and hearth extension with a non-
combustible material (see Figure 3). 
 WARNING: Hearth extension 
is to be installed only as shown 
in Figure 3.
Fireplace insTallaTion
Continued
Figure 3 - Hearth Extension
Seal Gap
Fireplace Front
Ember Protector
Fireplace Front 
Raised Hearth
Fireplace Front 
Elevated
Ember Protector
Ember Protector
Seal Gap
Hearth 
Extension
MANTELS
A mantel may be installed if desired (see Figure 4). 
Woodwork such as wood trims, mantels or any other 
combustible material projecting from the front face 
must not be placed within 12" of the fireplace open-
ing. Combustible materials above 12" and projecting 
more than 1 
1
/
2
" from the fireplace must not be placed 
less than 15" from the top opening of the fireplace 
(NFPA STD 211, Sec. 7-3.3.3).
Mantels or any other combustible material also 
may come up to the side edge of the black metal 
face of the fireplace just as long as the projection 
from the front face fall within the limit shown in 
Figure 4.
1
/
4
" Ref.
15" Min.
1" Min.
1
1
/
" Max.
3" Nom.
33°
Combustible 
Material
Safe 
Zone for 
Projection of 
Combustible 
Materials
Fireplace 
Opening
Upper 
Section of 
Fireplace
Figure 4 - Mantel Clearances to 
Combustible Material
FIREBOX
SAFE ZONE
Top View of Fireplace
3" Max.
4.5"
Min. to 
Perpendicular 
Side Wall 
1"
7.75"
33°
Combustible 
Material Must 
Not Overlap 
Front Face
6"
Ref.