VenTing insTallaTion
Continued
Figure 9 - Elbow Offset
B
A
Screws
FIRESTOP SPACERS (FS-10)
Firestop spacers are required at each point where 
the chimney penetrates a floor space. Their purpose 
is to establish and maintain the required clearance 
between the chimney and the combustible materials. 
When the pipe passes through a framed opening into 
a living space above, the firestop must be placed onto 
the ceiling from below as shown in Figure 10.
They also provide complete separation from one floor 
space to another or attic space as required by most 
codes. When the double wall pipe passes through a 
framed opening into an attic space, the firestop must 
be placed into an attic floor as shown in Figure 11.
Figure 10 - Firestop Spacer with Living 
Space Above Ceiling
Figure 11 - Firestop Spacer with Attic 
Space Above Ceiling
Existing 
Ceiling 
Frame
Firestop 
Spacer
Screws or 
Staples 
(Min. of 8)
Firestop 
Spacer
Screws or Staples 
(Min. of 8)
PENETRATING THE ROOF
To maintain a 1" clearance to the pipe on a roof 
with a pitch, a rectangular opening must be cut.
1.  Determine the center point through which the 
pipe will penetrate the roof.
2.  Determine the center point of the roof. Pitch 
is the distance the roof drops over a given 
span, usually 12". A 6/12 pitch means that 
the roof drops 6" for each 12" one measure 
horizontally down from the roof rafters.
3.  Use the roof opening chart (Figure 12) to 
determine  the  correct  opening  length  and 
flashing required.
4.  Remove  the  shingles  around  the  opening 
measured. Cut out this section.
5.  Add the next sections of the pipe until the 
end penetrates the roof line. Check to see that 
the proper clearances are maintained. Extend 
chimney by adding sections of double wall 
pipe until pipe is minimum of 30" above the 
highest point of the roof cutout. Termination 
and  chimney  must  extend  a  minimum  of 
36" above the highest point where it passes 
through the roof.
19.5" Min.
30" Min.
2" Min.
2" Min.
2" Min.
Opening "A"
Pitch
Slope
Opening 
"A" Max. 
Used Flashing
Model No. 
Flat
19.5"
V6F-10DM
0-6/1
6.6°
"
V6F-10DM
6/1-
1/1
45.0°
7"
V12F-10DM
Existing 
Ceiling 
Frame
Figure 12 - Roof Opening Measurements
FLASHING INSTALLATION (V6F-10DM 
OR V12F-10DM)
Determine the flashing to be used with the roof 
opening chart. Slide flashing over pipe until base 
is flat against roof. Replace as many shingles as 
needed to cover exposed area and flashing base. 
Secure in position by nailing through shingles (see 
Figure 13, page 10). DO NOT NAIL THROUGH 
FLASHING CONE.