three or four sheet metal screws (not supplied) equal-
ly distributed around the circumference of the duct. All
ducting should be self-supported. The filter housing is
not designed to support the air duct.
TruSeal™ Combustion Air
In  certain  applications  it  may  be  necessary  to  utilize
the TruSeal option (sales order option D-21 or D-22)
and  duct  the  combustion  air  directly  to  the  blower.
Combustion air may be ducted directly to the heater by
using  PVC,  CPVC  or  sealed  single-wall  galvanized
ducting. The duct will attach directly to the air collar lo-
cated  on  the  side  of  the  heater,  using  three  or  four
sheet  metal  screws  (not  supplied)  equally  positioned
around the circumference of the duct. The screws and
duct  connection  point  must  be  sealed  with  RTV  (not
supplied).  An  in-line  intake  air  filter  kit  (sales  order
option  D-17)  must  be  installed  in  the  combustion  air
duct. TruSeal is generally used when damaging con-
taminants are present in the mechanical room.
TruSeal heater connection points are available as fol-
lows:
302B & 402B
Right side only
502B to 902B Left side - standard
Right side - optional
Conventional Combustion Air
Supply
U.S. Installations
All Air from Inside the Building
The confined space shall be provided with TWO per-
manent  openings  communicating  directly  with  an
additional room(s) of sufficient volume so that the com-
bined  volume  of  all  spaces  meets  the  criteria  for  a
room large in comparison (NFGC). The total input of all
gas utilization equipment installed in the combined 
CAUTION: Use  TrueSeal  combustion  air  if
damaging  airborne  contaminants  are  or  will  be
present  in  the  heater  area.  See  the  Appendix
regarding air contamination.
space  shall  be  considered  in  making  this  determina-
tion. Each opening shall have a minimum free area of
1 in.
per 1,000 BTUH (2,225 mm
2
per kW) of the total
input rating of all gas utilization equipment in the con-
fined space, but not less than 100 in.
2
(645 cm
2
). One
opening shall commence within 12 in. (305 mm) of the
top,  and  one  opening  shall  commence  within  12  in.
(305  mm)  of  the  bottom  of  the  enclosure.  The  mini-
mum dimension of air openings shall be not less than
3 in. (76 mm) in any direction.
All Air from Outdoors
The  confined  space  shall  communicate  with  the  out-
doors  in  accordance  with  one  of  the  methods  below.
The minimum dimension of air openings shall not be
less than 3 in. (76 mm) in any direction. Where ducts
are  used,  they  shall  be  of  the  same  cross-sectional
area as the net free area of the openings to which they
connect.
1. Two  permanent  openings,  one  commencing
within  12  in.  (305  mm)  of  the  top,  and  one  com-
mencing  within  12  in.  (305  mm)  of  the  bottom  of
the  enclosure,  shall  be  provided.  The  openings
shall  communicate  directly,  or  by  ducts,  with  the
outdoors or spaces (crawl or attic) that freely com-
municate with the outdoors.
a. Where  directly  communicating  with  the  out-
doors  or  where  communicating  to  the
outdoors through vertical ducts, each opening
shall  have  a  minimum  free  area  of  1  in.
2
per
4,000 BTUH (550 mm
2
per kW) of total input
rating of all equipment in the enclosure.
b. Where  communicating  with  the  outdoors
through  horizontal  ducts,  each  opening  shall
have a minimum free area of 1 in.
2
per 2,000
BTUH  (1,100  mm
2
per  kW)  of  total  input  rat-
ing of all equipment in the enclosure.
2. One permanent opening, commencing within 12
in. (305 mm) of the top of the enclosure, shall be
permitted where the equipment has clearances of
at least 1 in. (25 mm) from the sides and back and
6 in. (152 mm) from the front of the appliance. The
opening  shall  directly  communicate  with  the  out-
doors  or  shall  communicate  through  a  vertical  or
horizontal  duct  to  the  outdoors  or  spaces  that
freely  communicate  with  the  outdoors,  and  shall
have a minimum free area of:
a. 1  in.
2
per  3,000  BTUH  (740  mm
2
per  kW)  of
the total input rating of all equipment located in
the enclosure, and
CAUTION:
This  type  of  installation  is
recommended  if  damaging  airborne  contaminants
are  or  will  be  present  in  the  heater  area.  See  the
Appendix regarding air contamination.