b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING:  Do  not  use  one  permanent  opening
method  if  the  equipment  room  is  under  negative
pressure  conditions  or  the  equipment  is  common
vented with other gas-fired appliances.
1. Ventilation  of  the  space  occupied  by  the  heater
shall be provided by an opening(s) for ventilation
air  at  the  highest  practical  point  communicating
with the outdoors. The total cross-sectional area of
such  an  opening(s)  shall  be  at  least  10%  of  the
area required in 2. and 3. (below), but in no case
shall the cross-sectional area be less than 10 in.
2
(65 cm
2
).
2. For heaters using a barometric damper in the vent
system  there  shall  be  a  permanent  air  supply
opening(s) having a cross section area of not less
than 1 in.
2
per 7,000 BTUH (320 mm
2
per kW) up
to  and  including  1  million  BTUH,  plus  1  in.
2
per
14,000  BTUH  (160  mm
2
per  kW)  in  excess  of  1
million  BTUH.  This  opening(s)  shall  be  either
located at or ducted to a point not more than 18 in.
(450 mm) nor less than 6 in. (152 mm) above the
floor level. The duct can also “goose neck” through
the roof. The duct is preferred to be straight down
and terminated 18 in. (450 mm) from the floor, but
not  near  piping.  This  air  supply  opening  require-
ment  shall  be  in  addition  to  the  air  opening  for
ventilation air required in 1. (above).
3. For heaters not using a barometric damper in the
vent  system,  and  when  air  supply  is  provided  by
natural air flow from outdoors for a power burner
and there is no draft regulator, drafthood or similar
flue  gas  dilution  device  installed  in  the  same
space, in addition to the opening for ventilation air
required in 1., there shall be a permanent air sup-
ply opening(s) having a total cross-sectional area 
CAUTION: All combustion air must be drawn from
the air outside of the building; the mechanical equip-
ment  room  must  communicate  directly  with  the
outdoors.
of not less than 1 in.
2
for each 30,000 BTUH mm
2
per  kW)  of  total  rated  input  of  the  burner(s),  and
the  location  of  the  opening(s)  shall  not  interfere
with  the  intended  purpose  of  the  opening(s)  for
ventilation  air  referred  to  in  (1).  This  opening(s)
can be ducted to a point not more than 18 in. (450
mm) nor less than 6 in. (152 mm) above the floor
level. The duct can also “goose neck” through the
roof. The duct is preferred to be straight down 18
in. (450 mm) from the floor, but not near piping.
4. Refer  to  the  B149  Installation  code  for  additional
information.
Water Piping
General
The heater should be located so that any water leaks
will not cause damage to the adjacent area or struc-
tures.
Reversing Water Connections
Follow these instructions to change the water connec-
tions  from  the  left-hand  side  (standard)  to  the
right-hand side.
1. Disconnect all electrical power from the heater (if
applicable).
2. Label all electrical connections and conduit lines.
This may include the flow switch, low water cut-off
probe and/or pump.
3. Disconnect or isolate the main gas pipe from the
heater (if applicable).
4. Remove  both  in/out  and  return  header  access
panels by removing all sheet metal screws.
WARNING: Care must be taken to ensure that the
equipment  room  is  not  under  negative  pressure
conditions  or  that  the  equipment  is  not  common-
vented with other gas-fired appliances.
NOTE: For  87%-efficiency  boilers,  see  special
instructions on page 40.
CAUTION: This  heater  requires  forced  water
circulation when the burner is operating. See Table H
and  Table  I  for  minimum  and  maximum  flow  rates
and  water  pump  selection.  The  pump  must  be
interlocked  with  the  heater  to  prevent  heater
operation without water circulation.
NOTE: Minimum pipe size for in/out connections is
2 in. Verify proper flow rates and ∆T as instructed in
this manual.
Canadian Installations