6. Reinstall the pipe cap on the left-hand end of the
main gas line.
7. Remove plastic cap from the right-hand side panel
and  reinstall  into  the  standard  main  gas  opening
located on the left-hand side of the heater.
8. Remove  the  rubber  grommet  from  the  left-hand-
side panel and reinstall into the standard main gas
opening,  located  on  the  right-hand  side  of  the
heater.
9. Install a coupling, nipple, union and sediment trap
onto the right-hand end of the main gas line and
then install the gas line, making sure that a manu-
al shut-off valve has been installed within 10 ft of
the heater.
10. Replace  the  left  and  right  front  panels  on  the
heater.
Gas Supply Pressure
A minimum of 5.0 in. WC and a maximum of 10.5 in.
WC upstream gas pressure is required under load and
no-load conditions for natural gas. A minimum of 11.0
in. WC and a maximum of 13.0 in. WC is required for
propane  gas. The  gas  pressure  regulator(s)  supplied
on the heater is for low-pressure service. If upstream
pressure  exceeds  14.0  in.  WC,  an  intermediate  gas
pressure  regulator,  of  the  lockup  type,  must  be
installed.
When connecting additional gas utilization equipment
to the gas piping system, the existing piping must be
checked  to  determine  if  it  has  adequate  capacity  for
the combined load.
The gas valve pressure regulator(s) on the heater are
nominally  preset  at  3.5  in.  WC  for  natural  gas,  and
10.5 in. WC for propane gas. The pressure at the gas
valve outlet tap, measured with a manometer, while in
Fig. 17: Gas Valve
operation should be 3.5 ± 0.1 in. WC for natural gas
and 10.5 in. ± 0.1 in. WC for propane gas. If an adjust-
ment is needed, remove the adjustment screw cover
and  turn  the  adjustment  screw  clockwise  to  increase
pressure or counter-clockwise to lower pressure.
Electrical Power Connections
Installations must follow these codes:
National  Electrical  Code  and  any  other  national,
state, provincial or local codes or regulations hav-
ing jurisdiction.
Safety wiring must be NEC Class 1.
Heater must be electrically grounded as required
by the NEC.
In Canada, CSA C22. 1 C.E.C. Part 1.
The heater is wired for 120 VAC, 8 amps in its basic
configuration.  Additional  options  may  increase  the
amp draw of the unit.  The voltage is indicated on the
tie-in leads. Consult the wiring dia-gram shipped with
the heater in the instruction packet. The remote tank
control stat, thermostat, or electronic heater control (as
applicable)  may  be  connected  to  the  stage  selector
terminal (See wiring diagram). 24 VAC is supplied to
this  connection  through  the  heater  trans-former.  DO
NOT attach any voltage to the stage selector termi-
nals. 
Before  starting  the  heater  check  to  ensure
proper voltage to the heater and pump.
Install  a  separate  disconnect  means  for  each  load.
Use appropriately sized wire as defined by NEC, CSA
and/or local code. All primary wiring should be at least
125% of minimum rating.
If any of the original wire as supplied with the heater
must be replaced, it must be replaced with 105°C wire
or its equivalent.
Field-Connected Controllers
It  is  strongly  recommended  that  all  individually-pow-
ered  control  modules  and  the  heater  should  be
supplied from the same power source.
NOTE: Field-supplied  isolation  relays  should  be
installed  when  field-connected  controllers  are
mounted more than 50 equivalent feet (18 Ga) from
heater.
CAUTION: For  proper  operation,  no  more  than  a
30% drop in gas supply pressure from no-load to full-
load  conditions  is  acceptable.  Under  no
circumstances  should  the  pressure  be  outside  the
listed operational range.