Check the Power Source
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX
AB = 108 VAC Minimum, 132 VAC MAX
BC = <1 VAC Maximum
If the heater does not have a factory-wired stage con-
troller, it is factory-wired in an on-off configuration with
other stage terminals jumpered.
To  field-connect  a  stage  controller,  remove  factory-
installed jumpers and wire stage controller as shown in
Fig. 21.
Making the Electrical Connections
Refer to Fig. 18-23.
1. Verify  that  circuit  breaker  is  properly  sized  by
referring to heater rating plate. A dedicated circuit
breaker should be provided.
23
CIRCUIT
BREAKER
WHITE
GROUND
BLACK
GREEN
A B C
Fig. 18: Wiring Connections
Fig. 19: Multi-meter
2. Turn off all power to the heater. Verify that power
has been turned off by testing with a multi-meter
prior to working with any electrical connections or
components.
3. Observe  proper  wire  colors  while  making  electri-
cal  connections.  Many  electronic  controls  are
polarity  sensitive.  Components  damaged  by
improper electrical installation are not covered by
warranty.
4. Provide  overload  protection  and  a  disconnect
means for equipment serviceability as required by
local and state code.
5. Install  heater  controls,  thermostats,  or  building
management  systems  in  accordance  with  the
applicable manufacturers’ instructions.
6. Conduit should not be used as the earth ground.
Field Wiring Connection
NOTE: A  grounding  electrode  conductor  shall  be
used  to  connect  the  equipment  grounding
conductors,  the  equipment  enclosures,  and  the
grounded  service  conductor  to  the  grounding
electrode.
CAUTION: Label  all  wires  prior  to  disconnection
when servicing controls. Wiring errors can cause im-
proper  and  dangerous  operation.  Verify  proper
operation after servicing.
Fig. 20: Wiring Location
WARNING: Using  a  multi-meter,  check  the
following  voltages  at  the  terminal  block  inside  the
unit. Make sure proper polarity is followed and house
ground is proven. (See Fig. 18.)
CAUTION: For  pumps  larger  than  3/4  HP,  a
separate circuit breaker may be required.