Raypak 302B 用户手册

下载
页码 60
25
SINGLE
STAGE
TANKSTAT
STAGE 1
CONNECTION
ATTACH STAGE 1 CONNECTIONS
ON HEATER TO THE SINGLE STAGE
TANKSTAT AS SHOWN IN THE DIAGRAM ABOVE.
Fig. 23: Single-Stage Tankstat
Consult the wiring diagram shipped with the heater in
the instruction packet or at the end of this section. The
stage-selector terminals are for the remote tank con-
trol through the heater’s 24 VAC transformer. DO NOT
attach any voltage to the stage-selector terminals.
Before starting the heater, check to ensure proper volt-
age to the heater and pump.
Venting
General
Flue Exhaust Tee
An optional Flue Exhaust Tee is available to facilitate
horizontal venting. Any reference to horizontal venting
that exits the back of the heater requires this tee. Refer
to Table L for the appropriate kit for your model.
NOTE: If any of the original wire supplied with the
heater  must  be  replaced,  it  must  be  replaced  with
similar sized 105°C wire or its equivalent.
NOTE: For  87%-efficiency  boilers,  see  special
instructions on page 40.
CAUTION: Proper installation of flue venting is criti-
cal for the safe and efficient operation of the heater.
Appliance Categories
Heaters are divided into four categories based on the
pressure produced in the exhaust and the likelihood of
condensate production in the vent.
Category I – A heater which operates with a non-pos-
itive  vent  static  pressure  and  with  a  vent  gas
temperature  that  avoids  excessive  condensate  pro-
duction in the vent.
Category II – A heater which operates with a non-pos-
itive  vent  static  pressure  and  with  a  vent  gas
temperature  that  may  cause  excessive  condensate
production in the vent.
Category III – A heater which operates with a positive
vent  pressure  and  with  a  vent  gas  temperature  that
avoids excessive condensate production in the vent.
Category IV – A heater which operates with a positive
vent  pressure  and  with  a  vent  gas  temperature  that
may  cause  excessive  condensate  production  in  the
vent.
See Table M for appliance category requirements.
Model
Diameter
Order Number
302B
5”
011838
402B-502B
6”
011839
652B, 752B,
902B
8”
011840
Table L: Flue Exhaust Tee Kits
NOTE: For  additional  information  on  appliance
categorization, see appropriate ANSI Z21 Standard
and  the  NFGC  (U.S.),  or  B149  (Canada),  or
applicable provisions of local building codes.