– 91 –
Ferrite core for sensor lead
Drawing-out port of lead wire
Card edge spacer
Card edge spacer
Ferrite core for fan motor
<Details of piping cover assembly and mounting>
<Details of sensor lead wire drawing>
<Details of fan motor lead wire drawing>
As shown in the figure,
hook the sensor lead wires 
to claw of the piping cover 
and then pass them so that 
they are stored in the groove.
After mounting the piping 
cover, check each lead wire 
does not hit the liquid pipe.
Turn up the sensor lead wires 
and fix surely with the cord clamp.
Fix the sensor lead wires with cord clamps (2 positions) so that 
it does not slacken at P.C. board side and draw wires as shown in the figure.
Please note the 
float SW lead wires are 
set at inner side of the 
fan motor lead wires.
Turn up the fan motor lead wires 
and fix surely with the cord clamp. 
(There should be no catching of 
lead wire by P.C. board.)
Clamp (yellow, gray, black) lead wires 
of the fan motor and arrange them 
as shown in the figure.
Cord clamp
Cord clamp
Tighten together the shield wires of the 
sensor lead wires and the remote controller. 
Be careful that other sensor does not fall out.
Adhere on the 
transformer.
Cord clamp
Arrow view E
E
No.
5
Part name
Control P.C.
board
Procedure
1. Detachment
1) Perform works of procedure  1  -1- and  2  -1.
2) Remove the connectors connected from the control P.C. board to other parts.
CN33 : Louver motor (5P, White)
CN34 : Float switch (3P, Red)
CN41 : Terminal block of remote controller (3P, Blue)
CN40 : Terminal block of crossover between inside and outside (5P, Black)
CN68 : Drain pump (3P, Blue)
CN67 : Terminal block of power supply (3P, Black)
CN101 : TC sensor (2P, Black)
CN102 : TCJ sensor (2P, Red)
CN104 : Room temp sensor (2P, Yellow)
CN333 : Fan motor power supply (5P, White)
CN334 : Fan motor position detection (5P, White)
NOTE)
Remove the connectors after
unlocking the lock of the housing.
3) Unlock the lock of the card
edge spacer (6 positions)
and then remove the
control P.C. board.
2. Attachment
1) Fix the control P.C. board to the card edge spacer. (6 positions)
2) Connect the connectors as original before being removed in item 1.
NOTE)
For drawing of each wire and position of ferrite core, perform wiring same as those before removing.
If there is incomplete drawing of wire, short or water leakage of the parts may be caused.
Remarks