commissioning
Operation 4 - Checking the CO2 at minimum gas fl ow
With the Test function active, 
rotate the encoder 
  to select 
the icom 
 and 
 . The 
boiler is forced to the minimum 
power.
Wait 1 minute for the boiler to 
stabilise before carrying out the 
combustion analyses.
If the CO2 value (%) read diff ers 
by 0.5 % from the value found, then adjust the gas valve following 
the instructions below, otherwise move directly onto operation 5.
Adjusting the gas valve to minimum gas fl ow
Remove  cap and adjust screw 2 by turning anti-clockwise in 
increments to reduce the CO2 level. Wait 1 minute after each 
adjustment for the CO2 
value to stabilise.
WARNING! this adjustment 
is sensitive: a rotation of a 1 
turn corresponds to 0.2% of 
CO2.
If the value measured 
corresponds to the 
value given in the table, 
adjustment is complete, 
otherwise start the setting 
procedure again.
Attention! If the value of the CO2 at the minum power has been 
changed, it is necessary repet the adjusting  at maximum gas 
fl ow.
Operation 5 - Ending the adjustment
Exit cleaning mode by pressing RESET.
Stop the draw-off .
Verify and repair any leaks of gas.
Refi t the front panel to the device.
Refi t the blanking cover at combustion test point.
menu 2 - Boiler parameters
submenu 3 - parameter 1  Maximum Heating Power adjustment
submenu 2 - parameter 0 Soft light Ignition
submenu 3 - parameter 5 Heating ignition delay
Maximum Heating Power adjustment 
 The maximum heating power can be adjusted to between the 
maximum power allowed by the boiler  and the minimum power). 
The display shows the value between 100% (“100” on the display) 
and 0% (“0”) of this interval.
To check the maximum heating power, access menu 2/sub menu 
3/parameter 1, check the value and, if necessary, modify it as 
indicated in the Gas Regulation table below. (See page 40 for more 
details).
Checking slow ignition power
The soft light can be adjusted between the maximum power 
(shown on the display as “100”, i.e. 100%)  and the minimum power 
(shown on the display as “1”, i.e. 1%).
To check the slow ignition power, access menu 2/sub menu 2/
parameter 0.
Heating ignition delay adjustment
This parameter – menu 2/sub menu 3/parameter 5 - can be used 
to manually (0) or automatically (1) set the delay time before the 
subsequent reignition of the burner after it has switched off  on 
reaching the desired temperature in central heating mode.
By selecting manual, it is possible to set the delay in minutes using 
the successive parameter (menu 2/sub menu 3/parameter 6), to a 
time between 0 and 7 minutes.
Automatic selection means that the boiler will establish the delay 
time based on the set-point temperature
Converting the appliance from Natural gas to LPG
These appliances are designed to operate with diff erent gas types.
The appliance must only be converted for use with a diff erent gas 
type by a Gas Safe Registered installer.
To convert the appliance to LPG: 
(use these instructions in conjunction with the Instruction sheet 
supplied with the LPG Kit).
1.  Electrically isolate the appliance
2. Turn off  the gas supply (fi g 1)
3.  Remove the outer case, lower the 
front control panel and remove 
the front combustion chamber 
panel.
4. Remove the green silencer (fi g 2)
5.  Disconnect the gas supply from 
the venturi assembly (fi g 3)
6. Inset the correct diaphragm 
(depending on the output of the 
appliance) into the venturi spigot  
7. Reassemble the gas supply onto 
the venture assembly (fi g 4)
8. Turn on gas supply and test for 
tightness
9. Purge gas supply
10. Turn the electrical supply on to 
the appliance.
11.Commission the appliance, check the working pressure is 
adequate then test and adjust the CO2  values at maximum and 
minimum output described in the commissioning section of the 
appliance installation instructions. Ensure the fl ue gas analyser 
used is calibrated and set for the gas group the appliance is 
being adjusted for.
12. Check the appliance for gas leaks using gas leak detection fl uid.
13. Affi
  x the label to the appliance that is supplied with the 
conversion kit.
CLAS HE EVO 38
CLAS HE EVO 30
CLAS HE EVO SYSTEM 30
CLAS HE EVO 24