Crown Boiler CWI138 用户手册

下载
页码 56
41
40
120 volts 
across 
terminals at 
circulator?
Do burners
shut dow n before 
gage temp 
exceeds high limit 
setting +15F?
Circulator 
start?
120 volts at 
C1&C2?
N
Remove t'stat or 
zone valve end 
sw itch w ires from 
T&TV terminals on 
L8124E.  Install 
temporary jumper 
across terminals T 
and TV
Does 
circulator 
run now ?
*Defective 
L8124E-see 
Note 6 on page 
36.
* Boiler w ater 
temperature 
has dropped 
below   low   limit 
setting
*Loose connection in t'stat or 
zone valve end sw itch w iring
*Defective t'stat or zone 
component
*T'stat or zone system 
misw ired-consult  t'stat or 
zone valve manufacturer's 
instructions
      N
Do burner and 
circulator shut 
dow n at end of 
call for heat?
END
Pull w ire off of T 
terminal on 
aquastat.  Does 
boiler shut dow n?
*T'stat or
zone valve 
w iring calling 
for heat
*T'stat w ires 
 shorted
* Boiler w ater 
temperature 
has dropped 
below   low   limit 
setting
*Internal boiler 
w iring 
problem, 
consult Crow n 
representative
*Defective 
L8124E
*Sensing bulb not
bottomed out in
w ell
24 volts 
across 
T&TV?
*Seized or 
defective 
circulator
*Bad electrical 
connection 
betw een C1 or 
C2 and 
circulator
     Y
       N
Y
N
Y
N
Y
Y
Y
N
N
Y
Y
N
Main 
burners 
light?
*Boiler w ater 
temperature 
exceeds high limit 
setting
* Defective 
L8124E
Y
N