Crown Boiler CWI138 用户手册

下载
页码 56
43
42
Does 
spark stop 
when pilot 
lights?
24 volts 
across 
terminals 2&3 
at S8600?
Spark 
across 
ignitor/sensor 
gap?
Y
Can you 
hear 
sparking?
*Faulty  
S8600 
module
*Break in 
spark cable 
insulation
*Break in pilot 
porcelain
*Incorrect pilot 
spark gap
*Loose 
connection in 
spark cable
*Loose 
ground 
connection
N
Pilot 
lights?
Y
N
N
*Defective 
S8600 module
24 volts 
across PV & 
MV/PV at gas 
valve?
*Defective EI 
wiring 
harness.
N
*Loose connection in 
ignition cable or 
ground wire
*Pilot electrode 
porcelain cracked
*Pilot flame not 
covering gap 
between electrode 
and grounding 
strap
*Low gas pressure 
at gas valve inlet
*Defective S8600 
module
Main 
burner 
lights?
N
Y
24VAC 
across 
terminals 1&2 
on S8600?
Y
N
N
*Defective
S8600 
module
 24 volts 
between MV & 
MV/PV on gas 
valve?
*Defective 
gas valve
*Defective EI 
harness
END
START 
(24 volts is present across 5 and 6 on S8600 
module, but main burners do not light)
N
Y
Y
N
Y
Y
Y
* Low line pressure
*Plugged, kinked or leaking 
pilot tubing
*Plugged pilot orifice
*Gas line not purged of air
*Defective pilot assembly
*Defective gas valve
Intermittent Ignition System Troubleshooting Chart
Caution: Read page 36 before
attempting to use this chart