ASHRAE Fundamentals for the area closest to 
the installation.  This value has a default of 10°F, 
and is adjustable between –60ºF to 32ºF.
e.  WWSD – The Warm Weather Shut Down feature 
is used only when the outdoor reset feature 
is selected. (OUTDR DESIGN = ON)  If the 
outdoor temperature rises above the WWSD 
value, WWSD will be displayed.  If a demand 
for heat is generated when the control is in the 
WWSD mode, the boiler will be disabled.  The 
default for the WWSD is 70ºF, but is adjustable 
from 35ºF to 100ºF.
f.  MIX MIN – This represents the minimum mix 
target supply temperature when the outdoor reset 
feature is selected. (OUTDR DESIGN = ON)  
This is the lowest temperature the controller is 
allowed to use as a MIX TARGET temperature.  
During mild conditions, if the RTC calculates a 
MIX TARGET below the MIX MIN, the target 
will be adjusted to match the MIX MIN setting.  
g.  MIX MAX – This represents the highest 
temperature allowed as the MIX TARGET 
temperature when the outdoor reset feature is 
selected. (OUTDR DESIGN = ON)  If the RTC 
calculates a MIX TARGET higher than the MIX 
MAX, the MIX TARGET will take the value of 
the MIX MAX.  Typically, this is set between 
200ºF and 220ºF.  The temperature must be set 
below the lowest permissible temperature for 
any system related component affected by boiler 
supply water.
h.  OPEN DELAY – This value represents the 
number of seconds required for the actuator to 
open through 90 degrees of rotation.  Leave in 
default value of 50 seconds.
i.  BOIL MIN – This is the minimum boiler return 
temperature allowed.  The minimum value has 
been set to 135ºF, adjustable to as high as 230ºF.  
The RTC will control the diverting valve while 
maintaining a minimum BOIL MIN temperature.  
Setting should remain at 135ºF unless a higher 
minimum boiler temperature is required.
j.  BOIL MIN DELAY – This represents the time 
(in seconds) required for warm-up during an 
initial cold start.  This prevents the counter 
from including cold start warm up time in the 
total boiler operation time below 135ºF.  This 
grace period is provided for every heat demand 
cycle until 135ºF has been sensed at the return 
sensor.  Once the return sensor has sensed a 
return temperature reading of 135ºF, after the 
heat demand cycle has initiated, the grace period 
is terminated.  The warm up time includes a 90 
seconds of pre-purge time.  Use the values in 
Table V for the correct application.
k.  PUMP DELAY – Pump delay represents the 
time (in seconds) for pump purge (boiler 
r
e
li
o
B
l
e
d
o
M
Y
A
L
E
D
N
I
M
L
I
O
B
)
s
d
n
o
c
e
S
(
3
0
-
4
2
0
4
5
4
0
-
4
2
0
6
4
5
0
-
4
2
0
1
4
6
0
-
4
2
0
7
3
7
0
-
4
2
0
6
3
8
0
-
4
2
0
4
3
9
0
-
4
2
0
2
3
0
1
-
4
2
0
1
3
1
1
-
4
2
0
0
3
2
1
-
4
2
0
9
2
circulator purge) after a heat demand cycle.  This 
minimizes the amount of boiler temperature 
overshoot at the end of a boiler cycle.  During 
the pump purge the diverting valve will 
continue to operate and prevent low return water 
temperatures from entering the boiler.  At the 
end of the pump purge period the diverting valve 
will be immediately closed.  The default PUMP 
DELAY is set to 30 seconds.
l.  UNITS – The temperature units can be changed 
to either Fahrenheit or Celsius. The default 
temperature unit is Fahrenheit.
4.  ERROR MESSAGES – Error messages are shown 
on the LED display.  The function in error will be 
shown as a black background label in the LED.  
Most of the errors indicate an open or short circuit, 
connected to the RTC.  The RTC Installation and 
Maintenance Manual identifies common errors.  
Cycle through the error messages and repair as 
required.
a.  Return Sensor Error – If the return water 
temperature sensor has been damaged or omitted, 
the BOIL item will be displayed as either a 
“short” or “open” circuit.  This will force the 
mixing device (i.e. 3-way valve) to run at a 
fixed 30% open position.  The system may not 
receive enough heat nor will it be fully protected, 
however a significant change will be obvious to 
occupants and/or operators.
b.  Operation Below Minimum – If the return sensor 
has been damaged or omitted, and the return 
water is allowed to return to the boiler below 
135ºF, the BOIL MIN field will be displayed 
along with ERR.  The failure must be identified 
and repaired immediately since the boiler 
has been operating in a condition that fosters 
premature boiler failure.
5.  COMPONENT EXERCISE - The RTC will exercise 
Table V:  Boil Min Delay Settings