24 volts across  1&4 
(blue&yellow) and  2&4 
(orange&yellow ) on 
damper end of 
harness?
N
Y
Main 
burners 
light?
24 volts across 
red damper lead 
and yellow 
transformer 
lead?
* Refer to standing pilot 
or intermittent ignition 
troubleshooting chart 
(page 39 or 40).
Defective damper
Defective or loose 
damper harness
Obstruction in 
path of damper 
blade
24 volts across 
standing pilot gas 
valve terminals or 
terminals  5&6 on 
S8600 module?
24 volts 
across spill 
switch?
*Chimney blockage
*Chimney system not 
contructed in accordance
with Parts 7 and 10 of 
National Fuel Gas Code .
*Down draft
*Inadequate combustion air 
supply in boiler room
Y
N
Y
24 volts 
across rollout 
switch?
*Loose electrical 
connection in spill 
switch or rollout 
switch wiring or gas 
valve common  
*Rollout switch open.  
Replace with exact 
replacement (see parts 
list).  Check for blocked 
heat exchanger.
Y
      N
      N
Y
N
Do burners shut 
down when water 
level drops below 
cut-off point?
END
*LWCO float bowl filled with 
mud
* Defective LWCO
DO NOT OPERATE BOILER 
UNTIL THIS PROBLEM IS 
CORRECTED
Do burners
shut down when 
pressure 
exceeds  limit 
setting?
Defective 
pressure limit 
control
Blockage in 
siphon tube 
Y
Y
N
N
Defective or 
loose damper 
harness 
* Defective or loose 
damper harness
Defective damper 
motor
*Obstruction in path 
of damper blade
N
Y