Standing Pilot Ignition System Troubleshooting Chart
Pilot lit?
Main 
burners 
light?
Y
Turn control on 
gas valve to 
PILOT.  Depress 
red button and 
light pilot.  Hold 
button for at 
least one 
minute.
Does pilot 
light?
N
*Pilot tubing 
blocked, kinked 
or leaking
*Pilot orifice 
blocked
*Gas line not 
purged of air 
*Pilot improperly 
adjusted.
Line pressure 
within the range 
indicated on 
boiler's rating 
plate?
Consult gas 
supplier.
Does pilot 
stay lit?
*Defective thermocouple 
*Pilot improperly 
adjusted
*Pilot tube blocked, kinked, or 
leaking
*Pilot orifice partially plugged
Y
N
N
     
Y
N
Turn control 
on gas valve 
to ON.
Y
END
*Defective gas 
valve
       Y
START
(24 VOLTS PRESENT ACROSS  TH AND TR 
ON GAS VALVE, BUT MAIN BURNERS DO 
NOT LIGHT)
Ensure knob 
on gas valve is 
set to ON
*Loose 
thermocouple 
connection at 
gas valve.
*Defective 
thermocouple.
*Condensation 
quenching pilot.
*Low line 
 pressure.
N
Y
N
Does pilot 
 stay lit when 
red button is 
released?
Disconnect 
thermocouple from 
gas valve. Connect a 
volt meter to the 
thermocouple. Light 
the pilot and hold 
down the red button 
while reading the 
voltage across the 
thermocouple.  
Is voltage at 
least 18mV?
*Loose or defective 
thermocouple 
connection at  gas valve
*Defective gas valve 
       Y
N
Caution: Read page 34 before
attempting to use this chart
39