Controls—General
Relief Valve
A  new  combination  temperature  and  pressure  (T&P)
relief  valve,  complying  with  the  Standard  for  Relief
Valves  and  Automatic  Gas  Shut-Off  Devices  for  Hot
Water  Supply  Systems,  ANSI  Z21.22,  must  be
installed in the opening provided on top of the storage
tank at the time of installation. No valve is to be placed
between the relief valve and the storage tank.
The pressure rating of the relief valve must not exceed
the 160 maximum working pressure indicated on the
water heater rating plate. The BTUH rating of the relief
valve  must  not  be  less  than  the  BTUH  input  of  the
heater.
Connect the outlet of the relief valve to a suitable open
drain.  The  discharge  line  must  pitch  downward  from
the valve to allow complete draining (by gravity) of the
relief  valve  and  discharge  line.  The  discharge  line
should be no smaller than the outlet of the valve. The
end  of  the  discharge  line  should  not  be  threaded  or
concealed, and should be protected from freezing. No
valve  of  any  type,  restriction  or  reducer  coupling,
should be installed in the discharge line. Local codes
shall govern installation of the relief valve.
Pump Time Delay
There are two versions of the Pump Time Delay. The
first is an electronic device that allows the operator to
set a variable time (3 to 10 minutes) for the pump to
run after the heater shuts off. See Fig. 21 (A). The time
is factory-set at 7 minutes and it can be re-adjusted in
the field.
The second version is a fully enclosed solid state Time
Delay  Relay  (TDR)  with  a  white  jumper  that  selects
one of two time delays. See Fig. 21 (B). If the jumper
is on pins 6 and 7 (default) the delay time is 5 minutes.
If the jumper is not on pins 6 and 7, the time delay is
10 minutes.
In a conventional system, when the tankstat is satis-
fied,  the  main  gas  valve  closes,  but  the  pump
continues  operating.  With  either  time  delay  relay  the
heater pump is programmed to continue running for an
optimum period of time in order to absorb the residual
heat  from  the  combustion  chamber  and  use  it  in  the
system. The pump then shuts off until the next call for
heat is received from the tankstat.
Electronic Ignition
The  intermittent  ignition  device  conserves  energy  by
automatically  extinguishing  the  pilot  when  desired
temperature is reached. When additional heat is need-
ed, the pilot re-ignites electrically, eliminating the fuel
costs  of  maintaining  a  constant  pilot. To  ensure  safe
operation,  the  gas  valve  cannot  open  until  the  pilot
relights and is confirmed.
Operating Controls
On models 0514-1826, models with mechanical mod-
ulating controls have one or more Robertshaw Unitrol
7000 Series hydraulic snap on thermostatic combina-
tion  gas  valves.  These  valves  have  the  pressure
regulator  and  24-volt  operator  built-in.  The  hydraulic
actuator will throttle the heater input to adjust the firing
rate  and  meet  the  required  load.  This,  in  effect,  pre-
vents  costly  fuel  consumption,  as  compared  to  an
NOTE: Pump  will  come  on  when  power  is  first
applied to heater.
Fig. 21: Economaster Time Delay Relays (TDR)
6
1
2
(A)
(B)
Table J: Electronic Ignition