on-off cycling heater. The valve has a remote capillary
bulb immersed in a well, at the header outlet, to main-
tain  a  constant  outlet  water  temperature.  When
multiple  valves  are  furnished,  they  can  be  staged  to
give greater flexibility of control. Standard factory set-
ting  is  at  position  5.  Consult  the  dial  setting  tag
attached  to  the  control  for  your  desired  temperature.
See Fig. 22 below.
Fig. 22: Dial Setting Tag
Fig. 23: Mechanical Modulating Valve Location—
Models 0724-1336
Fig. 24: Motorized Gas Valve Location—Model 3001
Limit Controls
High Limit
The heater is equipped with a manual reset High Limit.
Push the reset button and set the limit(s) to 30°F–40°F
above  desired  operating  temperature.  Maximum  set-
ting is 200°F; other options may be available.
Flow Switch
This dual-purpose control shuts off the heater in case
of pump failure or low water condition and is strongly
recommended. It is mounted and wired in series to the
main gas valve.
Fig. 25: High Limit
NOTE: The flow switch is a safety device and not a
control.  Do  not  operate  the  heater  with  flows  less
than the minimums stated in this manual.
Fig. 26: Flow Switch