Raypak 1334001 用户手册

下载
页码 52
7
INSTALLATION
Installation Codes
Installation must be in accordance with local codes, or,
in the absence of local codes, with the latest editions
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
and  the  National  Electrical  Code,  ANSI/NFPA  70.  In
Canada  installations  must  conform  with  the  current
CAN/CSA  B149  and  the  Canadian  Electrical  Code
Part 1 CSA C22.2 No.1. Where required by the author-
ity having jurisdiction, the installation must conform to
American  Society  of  Mechanical  Engineers  Safety
Code  for  Controls  and  Safety  Devices  for
Automatically Fired Heaters, CSD-1.
Installation base
The  heater  should  be  mounted  on  a  level,  non-com-
bustible  surface.  Heater  must  not  be  installed  on
carpeting.  The  heater  can  be  installed  on  a  com-
bustible surface only when the appropriate listed floor
shield base is provided. An optional listed floor shield
base is available for factory installation with the heater
on all indoor models. Do NOT use the shipping base
crate as an installation base.
In addition, the heater shall be installed such that the
gas  ignition  system  components  are  protected  from
water (dripping, spraying, rain, etc.) during appliance
operation and service (circulator replacement, control
replacement, etc.).
NOTE: The  heater  should  be  located  in  an  area
where water leakage will not result in damage to the
area  adjacent  to  the  appliance  or  to  the  structure.
When  such  locations  cannot  be  avoided,  it  is
recommended that a suitable drain pan, adequately
drained,  be  installed  under  the  appliance.  The  pan
must not restrict air flow.
General Specifications
The  Raypak  water  heaters  are  design  certified  and
tested under the latest requirements of the American
National  Standard,  ANSI  Z21.10.3/CSA  4.3.  Each
heater  has  been  constructed  and  pressure  tested  in
accordance with the requirements of Section IV of the
American Society of Mechanical Engineers Code, and
factory fire tested.
All Models (Approved)
All models are National Board approved. Temperature
and  pressure  gauge  is  standard.  Intermittent  ignition
device is standard on models 0514 and up.
Model  0133  has  4-pass  heat  exchanger,  1  tube  per
pass.
Models  0181-0401  have  2-pass  heat  exchangers,  5
tubes first pass, 4 tubes second pass.
Models  0514-1826  have  2-pass  heat  exchangers,  5
tubes first pass, 4 tubes second pass.
Models  2100-4001  have  2-pass  heat  exchangers,  9
tubes per pass.
Models 0926-4001 have optional single pass with cast
iron headers only.
Hot Water Supply Heaters
All Raypak hot water supply heaters are ASME rated
and design certified as hot water heaters, with 125 PSI
pressure relief valves.
TYPE WH1 with ON/OFF CONTROLS
Models 0133-4001
To be used with storage tank systems. Available with
integrally mounted pump, factory mounted and wired
for models 0133-1826. Models 0181, 0261, 0331 and
0401 are Low NOx Hot Water Heaters.
TYPE WH2 with MODULATING 
CONTROLS
Models 0133-4001
Hot water supply heater with 110°-170°F gas modula-
tion. Available  with  integrally  mounted  pump,  factory
mounted and wired for models 0133-1826. To be used
with storage tank systems.
TYPE WH3 with 2-STAGE 
CONTROLS
Models 0181-4001
Hot water supply heater with low-high fire for 2-stage
control. Available with integrally mounted pump, facto-
ry  mounted  and  wired  for  models  0181-1826.  To  be
used with storage tank systems.