Air Intake Assembly 
The air intake system consists of a field supplied 4 
inch diameter stainless steel, Schedule 40 PVC, ABS 
or CPVC pipe.  A maximum 6 feet of semi-rigid 
flexible aluminum ducting can also be used.  Foil 
wrapped dryer vent and cell core products are not 
authorized. 
The air intake has a zero clearance to combustibles. 
Air Intake Connection 
1.  Drill 2 small holes at the end of the air intake 
pipe. 
2.  Slide the pipe over the air intake terminal. 
3.  Using a level, ensure the pipe is straight up and 
down. 
4.  With self tapping screws, attach the pipe to the air 
intake terminal. 
5.  Apply a bead of silicone around the pipe and air 
intake terminal, ensuring an air tight connection. 
Exhaust Pipe Assembly 
Refer to the manufacturer’s installation instructions for 
the specific exhaust vent system. 
Venting Clearances to Combustibles 
Vent Size 
Enclosed Unenclosed 
Horizontal & 
Vertical 
Horizontal & 
Vertical 
4" (102 mm) 
4" (102 mm) 
1" (26 mm) 
4
3
1
2
COMBUSTION AIR /
INTAKE
EXHAUST
SLOPE INTAKE AND EXHAUST
TOWARD OUTSIDE TERMINATION
MINIMUM 1/4" PER FOOT
Horizontal Terminations 
The air intake must be located in relation to the exhaust as shown below.  The air intake must angle 1/4 inch per 
foot to the termination to prevent entry of rain. 
Flue Installation (R98LSiR98LSi-ASME) 
      
           
8
” 
6
” 
Intake 
Optional 
Intake 
Vent 
The vent termination and air 
intake must be in the same 
pressure zone and face the 
same direction.