Figure 32 - External Regulator with Vent Pointing Down 
(Propane/LP Only)
 
FIREPLACE INSTALLATION 
CHECK GAS TYPE
Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer where 
you purchased the fireplace for proper fireplace for your gas type or conversion kit.
INSTALLING GAS PIPING TO FIREPLACE / BURNER SYSTEM LOCATION
INSTALLATION ITEMS NEEDED
Before installing fireplace and burner system, make sure you have the items listed below.
•  External regulator (supplied by installer) 
•  Piping (check local codes) 
•  Sealant (resistant to propane/LP gas) 
•  Equipment shutoff valve* 
•  Test gauge connection* 
•  Sediment trap (recommended) 
•  Tee joint 
•  Pipe wrench
• 
A
pproved flexible gas line with gas connector (if allowed by local codes — not provided)
*  A CSA design-certified equipment shutoff valve with 
1
/
8
" NPT tap is an acceptable alternative to test gauge connection. 
Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming 
gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of 
WC. If you do not reduce incoming gas 
pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 
32. 
Pointing the vent down protects it from freezing rain or sleet. 
External 
Regulator 
100 lb. (min) 
Propane/LP 
Supply Tank 
Vent Pointing 
Down
When using copper or flex connectors use only fittings approved 
for gas connections. The gas control inlet is 
3
/
8
" NPT.
A  qualified  installer  or  service  person  must 
connect appliance to gas supply. Follow all 
local codes. 
WARNING
For  propane/LP  units,  never  connect  fireplace  directly  to  the  propane/LP  supply.  This 
burner system requires an external regulator (not supplied). Install the external regulator 
between the burner system and propane/LP supply. 
CAUTION
Use  only  new  black  iron  or  steel  pipe.  Internally 
tinned copper or copper tubing can be used per 
National  Fuel  Code,  section  2.6.3,  providing  gas 
meets hydrogen sulfide limits, and where permitted 
by local codes. Gas piping system must be sized 
to provide minimum inlet pressure (listed on data 
plate) at the maximum flow rate (BTU/hr). Undue 
pressure loss will occur if the pipe is too small.
CAUTION