VERTICAL THROUGH-THE-ROOF APPLICATIONS — RIGID VENTING ONLY  
This Gas Fireplace has been approved for,
•     Vertical installations up to 50' (15m) in height. Up to a 10' (3m) horizontal vent run can be installed within the vent system 
using a maximum of two 90° elbows. See Figure 25.
Figure 25- Support Straps for Horizontal Runs
VENT INSTALLATION 
Figure 26 - Maximum Elbow Usage 
•     Up  to  two  45°  elbows  may  be  used  within  the 
horizontal  run.  For  each  45°  elbow  used  on  the 
horizontal plane, the maximum horizontal length 
must be reduced by 18" (450mm). 
Example: Maximum horizontal length 
 
No elbows   =   10’ (3m)
 
1x45° elbows   =   8.5’ (2.6m)
 
2x45° elbows   =   7’ (2.1m)
•     A  minimum  of  an  8'  (2.5m)  vertical  rise  is 
required if venting through the roof.
•     Two sets of 45°elbows offsets may be used within 
the vertical sections. From 0 to a maximum of 8' 
(2.5 m) of vent pipe can be used between elbows. 
See Figure 26.
•     91, 92 series fireplaces allow for offsets. This 
application will require that you first determine the 
roof pitch and use the appropriate starter kit. 
•     The  maximum  angular  variation  allowed  in  the 
system is 270°. See Figure 26.
•     The minimum height of the vent above the high-
est  point  of  penetration  through  the  roof  is  2' 
(610mm). 
40' Maximum Height
8' Minimum Height 
40' Maximum Height
8' Minimum Height 
10'
Maximum 
10'
Maximum 
1
2
3
4
1
2
3
4
Support Straps
Every 3'
Support Straps
Every 3'
Example: 
Elbow 1   =   45°
 
Elbow 2   =   45°
 
Elbow 3   =   90°
 
Elbow 4   =   90°
Total Angular Variation  
=   270°
Support 
Straps
Every 
5'Vertical
Restrictor 
Disk
Restrictor 
Disk
Restrictor Disk
 
RESTRICTOR DISC
NOTE:  The  restrictor  disc  
included with the installation 
instructions  should  be  used 
on  vertically  terminating 
installations only.
Install the restrictor disc into 
the flue collar of the appliance 
with the bar horizontal.