Mastic 91N 用户手册

下载
页码 42
22                                                                                                                                                       
L100001
                                                                                                                                                                            
23
 
VENT INSTALLATION 
INSTALLATION FOR VERTICAL TERMINATION 
1.  Determine the route your vertical venting will take. If ceiling joist, 
roof rafters or other framing will obstruct the venting system, consider 
an offset. See Figure 27 to avoid cutting load bearing members. 
NOTE: Pay special attention to these installation instructions for 
required clearances (air space) to combustibles when passing 
through ceilings, walls, roofs, enclosures, attic rafters, etc. Do 
not pack air spaces with insulation. Also note maximum vertical 
rise of the venting system and any maximum horizontal offset 
limitations.  Offsets  must  fall  within  the  parameters  shows  in 
Figure 10, page 16.
2.  Set fireplace in desired location. Drop a 
plumb line 
down from the 
ceiling to the position of the flue exit. Mark the center point where 
the vent will penetrate the ceiling. Drill a small locating hole a this 
point. 
 
Drop a plumb line from the inside of the roof to the ceiling locat-
ing hole in the ceiling. Mark the center point where the vent will 
penetrate the roof. Drill a small locating hole at this point. 
FLAT CEILING INSTALLATION
1.  Cut a 9
1
/
2
" (241mm) square hole in the ceiling using the locating 
hole as a center point The opening should be framed to 9
1
/
2
"x9
1
/
2
(241mm x 241mm) inside dimensions as shown in Figure 12, page 
17 
using framing lumber the same size as the ceiling joist. If the 
area above the ceiling is an insulated ceiling or a room, nail firestop 
from the top side. This prevents loose insulation from falling into 
the required clearance space. See Figure 28. Otherwise, install firestop 
below the framed hole. The firestop should be installed with no less 
than three nails per side. See Figure 29. 
2.  Assemble the desired lengths of pipe and elbows necessary to reach 
from the burner system flue up through the firestop. Be sure pipe and 
elbow connections are fully twist-locked. See Figure 13, page 17. 
3.  Cut a hole in the roof using the locating hole as a center point. 
(Cover any exposed open vent pipes before cutting hole in roof). 
The 9
1
/
2
"x9
1/2
" (241mm x 241mm) hole must be measured on the 
horizontal. Actual length may be larger depending on the pitch of 
the roof. There must be a 1" minimum clearance from the vent 
pipe to combustible materials. (Insulation should be considered a 
combustible material). Frame the opening as shown in Figure 12 on 
page 17.
Figure 27 - Offset with Wall Strap and 45 Elbows 
Roof 
Flashing 
Wall Strap 
45° Elbows 
Ceiling Firstop 
Figure 28- If area above is a room, install firestop 
above framed hole as shown 
Figure 29 - If area above is not a room, install firestop 
below framed hole as shown 
Continued on next page 
Firestop 
Nails
Nails
Firestop