7.3.2. ALMSTAT
SYNTAX
<address>ALSTAT<CR>
DESCRIPTION
Returns the current status of both of the concentration alarms.
0= Inactive
1= Active
DATA PARAMETERS SENT
None
RESPONSE
<address>:<HI alarm state>,<HI-HI alarm state>#<checksum><CR>
EXAMPLE
Command:
1ALMSTAT<CR>
Response:
1:0,0#247<CR>
- Both concentration alarms are INACTIVE
1:1,0#248<CR>
- The HI alarm is ACTIVE and the HI-HI alarm is INACTIVE
1:1,1#249<CR>
- Both concentration alarms are ACTIVE