ga6HB/6HeB 60 hz gENERATOR • OpERATiON ANd pARTs mANuAl — REv. #0 (03/13/14) — pAgE 23
oPeRaTion
6.  Press the generator's pushbutton start switch 
(Figure 17) and listen for the engine to start.
Figure 17. Start Switch (GA6HEB Only)
7.  If the engine has started, slowly return the choke lever  
(Figure 14) to the 
OpeN position. If the engine has not 
started repeat steps 1 through 6.
8.  Before the generator is placed into operation, run the 
engine for 3-5 minutes. Check for abnormal smells, 
fuel leaks, and noises that would associate with lose 
components.
9.  Place idle control switch (Figure 18) in the 
OFF  
position. This will allow the engine speed to run at about 
3600 RPM's.
Figure 18. Idle Control Switch (OFF)
OFF
ON
OFF
GA-6HB
GA-6HEB
 NOTICE
Placing the idle control switch in the 
OFF position 
(Figure 18) allows the  engine to operate at a maximum 
speed of about 3600 RPM's. 
When the idle control switch (Figure 19) is placed in the 
up position (
ON), the generator will run at idle speed 
(2200 RPM's) until a load is applied, at that time the 
engine speed will increase to 3600 RPM's as long as 
a load is being applied. 
When the load is not in use, the engine speed will drop 
back to the idle mode after about 3 seconds.
Figure 19. Idle Control switch (ON)
10.  Place main circuit breaker (Figure 20) in the 
ON 
position.
Figure 20. Main Circuit Breaker (ON)
11.  Read voltmeter on front panel of generator (Figure 21) 
and verify that 120 VAC is displayed. Using an external 
voltmeter as shown in Figure 19, verify that 120 VAC 
is present at the 120V twist-lock and GFCI duplex 
receptacles.
Figure 21. 120V Twist-Lock/GFCI Receptacles
ON
OFF
GA-6HB
GA-6HEB
ON
OFF
ON
120V
OFF
V~
V
300 mV
A
A~
V
COM
120 VAC
GFCI
L5-30R
120
V
G
W
120VAC
X