4.0 TROUBLESHOOTING 
 
If the StarInverter’s “STAND BY” LED remains solid red or blinking red for a prolonged 
period (more than 24 hours), the AC breaker or AC disconnect should be turned to the 
OFF position for 1 minute and then returned to the ON position.  After reset, if both AC 
and DC operational specifications are met, the red LED is OFF and the green LED is 
illuminated.  If after AC is reset the red “STAND BY” light remains illuminated or blinking, 
double-check all connections and voltage levels. If the red “STAND BY” light is still 
illuminated or blinking, contact your authorized dealer/distributor for product support.  
 
The LEDs will display the following light indicators when a fault has occurred: 
 
 
 
RED FLASHING 
 
Inverter has a fault, refer to fault codes below for                           
  
 
diagnosis 
GREEN SOLID, RED FLASHING  Inverter has faulted, operational DC range is present. 
AC/grid-related fault 
RED SOLID   
 
 
DC Limit is too low; inverter is in “STAND BY” mode. 
 
In addition to the above fault indicators, the PVP Command Center software will indicate 
system status.  If a fault has occurred, a fault message as well as the corresponding code 
will be displayed. 
 
The vacuum fluorescent display will provide the following codes when a fault has 
occurred: 
 
First Code:
 
PDPA FAULT 
0x8000 
power module generated fault 
VOLTAGE FAULT 
 
 
0x1000 
Code 3 will contain further information 
GROUND FAULT 
 
 
0x0400  
LOW POWER FAULT 
0x0200 
array power too low for max power 
 
 
tracking                                                                        
CPU LOAD FAULT   
 
0x0100 software 
overload 
OVERCURRENT FAULT 
 
0x0040  
PRECHARGE FAULT  
 
0x0020  
HEATSINK TEMP FAULT   
0x0004 
AMBIENT TEMP FAULT 
 
0x0001 
 
Second Code:   
 
 
0x0000 
will always remain zero  
 
Third Code:  (Voltage Faults)
 
AC SENSE 
 
 
0x0800 
AC voltage sensing missing per UL or            
                                                               Ground Fault 
AC OVER VOLTAGE FAULT 
0x0400 
AC UNDER VOLTAGE FAULT 0x0200 
AC UNDER FREQENCY FAULT 
0x0100 
AC OVER FREQUENCY FAULT 
0x0080 
 
 
DC UNDER VOLTAGE FAULT 
0x0020 
array voltage too low 
DC OVER VOLTAGE FAULT 
0x0010 
P15 
FAULT 
   0x0002 
+15V supply out of specifications 
PS 
FAULT 
   0x0001 
+5V supply out of specifications 
 
As indicated above, there are three 16-bit codes assigned to describe faults, one of which will 
always remain zero.  More than one fault can be represented at a time.  This will be indicated by a 
fault with a code equal to the sum of the individual faults. 
PV Powered LLC 
19 
18-28-405