FP-AI-110 and cFP-AI-110
(10 lb
⋅ in.) of torque. The nylon coating on the screws prevents 
them from loosening.
Figure 2.  Installing the cFP-AI-110
Wiring the [c]FP-AI-110
The FP-TB-x terminal base has connections for each of the eight 
input channels and for an external power supply to power field 
devices. The cFP-CB-x connector block provides the same 
connections. Each channel has separate input terminals for voltage 
(V
IN
) and current (I
IN
) input. Voltage and current inputs are 
referenced to the COM terminals, which are internally connected 
to each other and to the C terminals. All eight V
SUP
 terminals are 
internally connected to each other and to the V terminals.
You can use a 10–30 VDC external supply to power field devices. 
Connect the external power supply to multiple V and V
SUP
 
terminals so that the maximum current through any V terminal 
1
cFP-DI-300
2
Captive  Screws
3
cFP Controller Module
4
Screw Holes
5
cFP  Backplane
2
2
1
3
5
4
4