FP-AI-110 and cFP-AI-110
Taking Measurements 
with the [c]FP-AI-110
The [c]FP-AI-110 has eight single-ended input channels. All eight 
channels share a common ground reference that is isolated from 
other modules in the FieldPoint system. Figure 3 shows the analog 
input circuitry on one channel.
Figure 3.   FP-AI-110 Analog Input Circuit
Measuring Voltage with the [c]FP-AI-110
The input ranges for voltage signals are 0–1 V, 0–5 V, 0–10 V, 
±60 mV, ±300 mV, ±1 V, ±5 V, and ±10 V.
Figure 4 shows how to connect a voltage source without an 
external power supply to one channel of the [c]FP-AI-110.
Figure 4.  Voltage Source without External Power Supply
V
IN
V
SUP
COM
I
IN
V
C
16-Bit
Isolated ADC
Filter
Filter
V
SUP
V
IN
V
C
To Analog
Input Circuitry
To Next Channel
>100 MΩ
Input
Impedance
COM
[c]FP-AI-110
Voltage
Source
+
I
IN