Alarm and fault messages 
4.2 Alarm and fault messages 
34 
Table 4-11 Fault 39 
(Alarm) DC link overvoltage 
Condition 
The CU has detected a DC voltage in excess of the 
permissible value 
Causes 
The measured DC voltage is too high  
o
  The available DC voltage is too high 
  The PV field has been connected 
incorrectly (the voltage rises too sharply at 
high temperatures, mostly under no load) 
o
  DC voltage measurement error  
  Parameter setting error (CU software) 
  Power pack defective (measured-value 
sensing) 
Adjust the parameter settings 
Replace the power pack 
Change the connection and/or the cabling of the PV field
 
Measures 
Connect a braking resistor 
 
Table 4-12 Fault 40 
(Alarm) Fast Stop 2; Fast Stop via customer terminal block 
Condition 
There is no signal at input 11/12 of the CU (green 
connector); transferred via Profibus to the S7; drive has 
not received an ON command. 
Causes 
No line voltage for Fast OFF 
o
  Fast Stop button has been pressed 
o
  Wire break in the Fast OFF circuit 
o
  No power supply for Fast OFF 
o
  Fire alarm system has been activated (if 
installed) 
o
 
No jumper on terminal strip X50 (if no Fast 
Stop button is connected)
 
Unlock the Fast Stop button. 
 
Measures 
Repair the cabling