Alarm and fault messages 
4.2 Alarm and fault messages 
36 
Table 4-16 Fault 63 
(Alarm) Direct current too high 
Condition 
The CU / S7 has detected a direct current in excess of 
the set permissible limit 
Parameter setting error (S7 software) 
Parameter setting error (CU software) 
Open circuit (detected by the S7 and indicated by this 
fault code) 
Causes 
Isolation amplifier is incorrectly set 
Adjust the parameter settings 
Repair the cabling 
 
Measures 
Set the isolation amplifier correctly 
 
Table 4-17 Fault 64 
(Alarm) Vdc or dVdc/dt too high 
Condition 
The CU has detected a DC voltage or an abrupt change 
in the DC voltage in excess of the permissible maximum 
value 
Parameter setting error  
Causes 
Connected DC voltage is too high 
Adjust the parameter settings 
Replace the power pack 
Check the connection and/or the cabling of the PV field 
 
Measures 
Install a braking resistor 
 
Table 4-18 Fault 65 
(Alarm) No checkback signal from the AC or DC contactor 
Condition 
Signal is missing at the relevant S7 inputs 
S7 relay output module defective 
Incorrect setting in the S7 
DC contactor is defective 
AC contactor is defective  
Fault in power supply 
Causes 
Wire break 
Replace the S7 relay output module 
Adjust the parameter setting 
Replace the defective contactor 
Repair the power supply 
 
Measures 
Repair the cabling