Hitachi hitachi series inverter 用户手册

下载
页码 99
 
23 
 
 
Sink/source logic of intelligent input terminals 
 
Sink or source logic is switched by a jumper wire as below.   
 
 
 
 
 
 
 
 
Wire size for control and relay terminals 
 
Use wires within the specifications listed below. For safe wiring and reliability, it is recommended 
to use ferrules, but if solid or stranded wire is used, stripping length should be 8mm. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 Solid 
mm
2
 (AWG) 
Stranded 
mm
2
 (AWG) 
Ferrule 
mm
2
 (AWG) 
Control logic 
terminal 
0.2 to 1.5 
(AWG 24 to 16) 
0.2 to 1.0 
(AWG 24 to 17) 
0.25 to 0.75 
(AWG 24 to 18) 
Relay terminal 
0.2 to 1.5 
(AWG 24 to 16) 
0.2 to 1.0 
(AWG 24 to 17) 
0.25 to 0.75 
(AWG 24 to 18) 
 
 
 
Control logic terminal 
Relay output terminal 
8mm 
Jumper wire
PLC  P24 
Sink logic
Jumper wire
 
PLC  P24 
Source logic