The alarm relay output can be configured in two main ways: 
• 
Trip/Power Loss Alarm – The alarm relay is configured as normally closed (
C036
=
01
by default, shown below (left). An external alarm circuit that detects broken wiring also 
as an alarm connects to [AL0] and [AL1]. After powerup and short delay (< 2 seconds), 
the relay energizes and the alarm circuit is OFF. Then, either an inverter trip event or 
an inverter power loss will de-energize the relay and open the alarm circuit 
• 
Trip Alarm – Alternatively, you can configure the relay as normally open (
C036
=
00
), 
shown below (right). An external alarm circuit that detects broken wiring also as an 
alarm connects to [AL0] and [AL2]. After powerup, the relay energizes only when an 
inverter trip event occurs, opening the alarm circuit. However, in this configuration, an 
inverter power loss does not open the alarm circuit. 
Be sure to use the relay configuration that is appropriate for your system design. Note that 
the external circuits shown assume that a closed circuit = no alarm condition (so that a 
broken wire also causes an alarm). However, some systems may require a closed circuit = 
alarm condition. In that case, then use the opposite terminal [AL1] or [AL2] from the ones 
shown. 
N.C. contacts (
C036
=
01
N.O. contacts (
C036
=
00
During normal operation 
When an alarm occurs or 
when power is OFF 
During normal operation 
or when power is OFF
When an alarm occurs 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
   
 
 
 
 
 
 
 
 
 
Power 
Run Mode 
AL0-AL1
AL0-AL2 
Power
Run Mode
AL0-AL1 
AL0-AL2 
 
 
ON Normal Closed Open 
ON Normal  Open Closed 
 
 
ON Trip Open 
Closed 
ON Trip Closed 
Open 
 
 
OFF –  Open 
Closed  OFF –  Open 
Closed 
 
   
 
 
 
 
 
 
 
 
 
AL1 
Power 
supply 
Load 
AL0 
AL2 
AL1
Power 
supply
Load 
AL0
AL2 
AL1
Power 
supply
Load
AL0
AL2
AL1 
Power 
supply 
Load 
AL0 
AL2