  Analog Input Operation
 
The WJ200 inverters provide for analog input to 
command the inverter frequency output value. 
The analog input terminal group includes the [L], 
[OI], [O], and [H] terminals on the control 
connector, which provide for Voltage [O] or 
Current [OI] input. All analog input signals must 
use the analog ground [L]. 
If you use either the voltage or current analog 
input, you must select one of them using the logic 
input terminal function [AT] analog type. Refer to 
the table on next page showing the activation of 
each analog input by combination of 
A005
 set 
parameter and [AT] terminal condition. The [AT] 
terminal function is covered in “Analog Input 
Current/Voltage Select” in section 4. Remember 
that you must also set 
A001
 = 
01 
to select analog 
input as the frequency source. 
 
NOTE: If no logic input terminal is configured for the [AT] function, then inverter recognizes 
that [AT]=OFF and MCU recognizes [O]+[OI] as analog input. 
 
Using an external potentiometer is a common way to 
control the inverter output frequency (and a good way 
to learn how to use the analog inputs). The 
potentiometer uses the built-in 10V reference [H] and 
the analog ground [L] for excitation, and the voltage 
input [O] for the signal. By default, the [AT] terminal 
selects the voltage input when it is OFF. 
Take care to use the proper resistance for the 
potentiometer, which is 1~2 k
Ω
, 2 Watts. 
Voltage Input – The voltage input circuit uses 
terminals [L] and [O]. Attach the signal cable’s 
shield wire only to terminal [L] on the inverter. 
Maintain the voltage within specifications (do not 
apply negative voltage). 
Current Input – The current input circuit uses 
terminals [OI] and [L]. The current comes from a 
sourcing  type transmitter; a sinking  type will not 
work! This means the current must flow into 
terminal [OI], and terminal [L] is the return back to 
the transmitter. The input impedance from [OI] to 
[L] is 100 Ohms. Attach the cable shield wire only 
to terminal [L] on the inverter. 
AM H O  OI  L 
+V Ref.
Voltage input 
Current input 
A GND 
AM H O OI L 
Freq. 
setting 
A001 
V/I input 
select
[AT]
+ -
4-20 mA 
0-10 V 
AM H O OI  L 
1 to 2k
Ω, 2W 
0 to 9.6 VDC, 
0 to 10V nominal 
AM  H  O  OI  L 
+ -
4 to 19.6 mA DC, 
4 to 20mA nominal 
AM  H  O  OI  L 
See I/O specs on page 21,22.