Hitachi hitachi series inverter 用户手册

下载
页码 99
 
82 
“P” Function 
Defaults 
Func. 
Code 
Name 
Description 
Run 
Mode 
Edit  Initial data  Units 
p041 
Speed / Torque control 
switching time 
Set range is 0 to 1000 ms 
U
 
0. 
ms 
P044 
Communication watchdog 
timer 
(for option) 
Set range is 0.00 to 99.99s 
U
 
1.00 
P045 
Inverter action on 
communication error 
(for option) 
00 (tripping), 
01 (tripping after decelerating and 
stopping the motor), 
02 (ignoring errors),   
03 (stopping the motor after 
free-running),  
04 (decelerating and stopping the 
motor) 
U
 
00 
P046 
DeviceNet polled I/O:   
Output instance number 
0-20 
U
 
P048 
Inverter action on 
communication idle mode 
00 (tripping), 
01 (tripping after decelerating and   
stopping the motor),   
02 (ignoring errors),   
03 (stopping the motor after 
free-running),  
04 (decelerating and stopping the 
motor) 
U
 
00 
P049 
Motor poles setting for RPM 
0/2/4/6/8/10/12/14/16/18/20/22/24/ 
26/28/30/32/34/36/38/40/42/44/46/48
U
 
Poles 
p055 
Pulse train input frequency 
scale setting 
Sets the pulse numbers at max. 
frequency, set range is 1.0~32.0 kHz
U
 
25.0 
kHz 
p056 
Pulse train input frequency 
filter time constant setting 
Set range is 0.01~2.00 sec. 
U
 
0.10 
sec 
p057 
Pulse train input bias setting 
Set range is –100~100 % 
U
 
0. 
p058 
Limitation of the pulse train 
input setting 
Set range is 0~100 % 
U
 
100. 
P060 
Multistage position 0 
 
Pulse
P061 
Multistage position 1 
 
Pulse
P062 
Multistage position 2 
 
Pulse
P063 
Multistage position 3 
 
Pulse
P064 
Multistage position 4 
 
Pulse
P065 
Multistage position 5 
 
Pulse
P066 
Multistage position 6 
 
Pulse
P067 
Multistage position 7 
P073 to P072 
(Displayed higher 4-digits only) 
 
Pulse
P068 
Homing mode selection 
00…Low speed mode 
01…High speed mode 
 
00 
P069 
Homing direction 
00…Forward rotation side 
01…Reverse rotation side 
 
01 
P070 
Low speed homing freq. 
0 to 10Hz 
 
5.00 
Hz 
P071 
High speed homing freq. 
0 to 400Hz 
 
5.00 
Hz