FieldServer FS-8700-21 用户手册

下载
页码 62
FS-8700-21 LonWorks Manual 
 
 
 
 
 
 
 
Page 13 of 62 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
5.2.6  Client Side Map Descriptor Example 
//    Client Side Map Descriptors 
 
 
 
 
 
 
 
 
 
 
 
 
Map_Descriptors 
 
 
 
 
 
 
 
 
 
 
 
Map_Descriptor_Name 
,Data_Array_Name 
,Data_Array_Offset 
,Lon_Function 
,Function 
,Node_Name 
,SNVT_Type 
,Nv_Delta_Value 
,Min_Scan_Time 
,Max_Scan_Time 
,Scan_Interval 
 
TempOut1 
,DA_FO_01 
,0 
,NVUOIMT 
,Wrbc 
,LON_1 
,SNVT_Temp_f 
,10 
,5 
,20 
,- 
 
TempOut2 
,DA_FO_01 
,1 
,NVUOIMX 
,Wrbc 
,LON_1 
,SNVT_Temp_f 
,- 
,- 
,- 
,- 
 
TempOut3 
,DA_FO_01 
,2 
,NVUOIMC 
,Wrbc 
,LON_1 
,SNVT_Temp_f 
,- 
,- 
,- 
,20 
 
TempIn 
,DA_FI_01 
,0 
,NVPIIMT 
,Rdbc 
,LON_1 
,SNVT_Temp_f 
,- 
,- 
,- 
,5 
 
This field 
determines the 
Map 
Descriptor’s 
function. See  
Section 5.1.2 
for more 
information. 
Required for Throttling Mode:  This field specifies the 
minimum change needed for a Network Variable’s 
value to invoke an NV Update. 
If found during Min_Scan_Time 
sampling (Throttling Mode) that 
Max_Scan_Time has elapsed since the 
last NV Update, a new NV Update will 
be transmitted. 
For Non-Throttled 
Client Map 
Descriptors the 
Scan_Interval 
determines the 
update rate. 
The Data Array will be 
sampled and evaluated for 
delta change once every 
Min_Scan_Time (seconds)