EXPLICIT CONFIGURATIONS 
6.1 
Special considerations 
With Explicit configuration, the FieldServer communicates directly with other devices by specifying the remote device address 
in the FieldServer configuration. 
All the Servers and their Clients need to be on the same domain to be able to communicate.  If the LonWorks device’s Node 
ID is not known, it may be read using a utility program e.g. NodeUtil or using a LonWorks Analyzer.  All the Client Node CSV 
files need to have their Subnet_ID and Node_ID parameters set to point to their respective Server Subnet and Node ID values.  
Once the FieldServers are restarted the network should function correctly. 
6.1.1  Map Descriptor Names (Network Variable Names)  
As a Server, the LonWorks driver provides a  table of Network Variables for other Nodes to read.   These Nodes access the 
variables  according  to  Index  numbers  which  are  automatically  assigned  by  the  driver  according  to  the  Map  Descriptor 
definition order in the configuration file.  The driver also creates an identification table for configuration nodes to read the 
name  and  types  of  variables  available  on  the  FieldServer.    Within  the  LonWorks  protocol,  this  table  size  is  limited  to  64K 
bytes.  If the application requires a large number of Server mappings (up to 4096), it will be necessary to limit the variable 
name length.  Each Server mapping requires 4 bytes plus the length of the name from this 64K block.   
6.1.2  Lon functions 
Explicit Map Descriptors are distinguished from Implicit Map Descriptors by the function used in the Lon_Function field of the 
Map Descriptor.  Depending on the nature and direction of Data Transfer needed different explicit functions are available as 
shown below  
NOTE:  
 
Function field MUST pair up with the Lon_Function field as shown in the table 
 
NMFETCHC is the preferred Lon Function for most applications. See Section 6.1.5 
 
Lon_Function  Description 
Function Field 
NVUI 
Network Variable Update Input 
SERVER 
NVPO 
Network Variable Polled Output 
NVPIEXC 
Network Variable Polled Input Explicitly addressed Continuously sent 
RDBC 
NVUOEXC 
Network Variable Update Output Explicitly addressed Continuously sent 
WRBC 
NVUOEXX 
Network Variable Update Output Explicitly addressed and sent on Change 
WRBX 
NVUOEXT 
Network Variable Update Output Explicitly addressed sent in Throttling Mode 
WRBC 
NMFETCHC 
Network Management Network Variable Fetch Continuously sent (Explicit Addressing only)  RDBC 
CFG_NVUI 
Configuration Network Variable Update Input 
SERVER 
 
6.1.3  SNVT_Index 
The SNVT_Index field must be specified for all explicitly addressed Client Map Descriptors.  These Client Map Descriptors use 
this field to index their relevant Map Descriptors on the Server side.