Appendix A. Useful Features 
Appendix A.1. Using UNVT’s 
UNVT’s are User-defined Network Variable Types and are defined in the configuration file by filling the SNVT_Type field with 
“UNVT”.  The UNVT’s size in bytes should also be added to the UNVT_Byte_Length field and the UNVT’s type number in the 
UNVT_ID field.  Valid UNVT_IDs are 0 and the range 146 to 255.  The UNVT_ID value will be substituted with the default value 
of 0 if the field is left empty.  Refer to the example in Section 6.2.3 
Appendix A.2. Using NV_Min, NV_Max etc. 
The NV_Min_Value, NV_Max_Value functionality were added to stop the propagation of ‘out of bounds’ network variables 
across  a  LonWorks  network.    NV  values  higher  than  assigned  by  the  NV_Max_Value  field  or  lower  than  assigned  by 
NV_Min_Value field will not be sent out on the network or copied to their relevant Data Arrays.  If one or both of these fields 
are not assigned values, limit checking will not be performed on that particular field.  This functionality applies only to SNVT's 
of either Floating point or Integer formats.  Refer to the examples in Sections 5.2.6 and 6.3.6. 
One or both of these fields can be linked to a configuration network variable update input in order to create an interoperable 
configuration property. For further information refer to Appendix A.5 
Appendix A.3. Throttling Mode 
When  the  Lon_Function  field  specifies  a  Throttling  Mode  Client  Map  Descriptor  the  NV_Delta_Value,  Min_Scan_Time  and 
Max_Scan_Time fields all need to be assigned values.   
When operating in Throttling Mode, a Network Variable’s value will be sampled at the Min_Scan_Time period.  If the value 
differs  by  an  amount  greater  than  or  equal  to  that  specified  by  the  NV_Delta_Value  field  from  the  previously  transmitted 
value, the NV update will be transmitted.  Otherwise an NV update will be only sent if the time since the last update is greater 
than or equal to the Max_Scan_Time field value.  Refer to the examples in Sections 5.2.6 and 6.3.6. 
This functionality applies only to SNVT’s of either Floating point or Integer formats. 
Appendix A.4. XIF Generation 
After start-up the FieldServer creates a XIF (version 4.0) according to the configuration loaded. This file is called fServer.xif 
and can be uploaded from the FieldServer using the RuiNet utility. 
The FieldServer’s XIF file is internally generated by the LonWorks driver using the information contained in the FieldServer’s 
configuration file (CONFIG.CSV).  It is not possible to download an externally created XIF file using NodeUtil or LonMaker.  It 
is  also  not  possible  to  download  any  type  of  externally  created  network  variables  default  values  file.    The  FieldServer’s 
configuration can be changed by uploading and editing the CONFIG.CSV file, and therefore the XIF file must be obtained by 
uploading it from the FieldServer. Remember that this XIF file will change whenever the configuration file has been changed, 
downloaded and the FieldServer restarted.