FieldServer FS-8700-21 用户手册

下载
页码 62
FS-8700-21 LonWorks Manual 
 
 
 
 
 
 
 
Page 25 of 62 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
Appendix A.5. Configuration Properties 
Configuration Properties are implemented on the FieldServer using configuration Network Variables. Configuration Network 
Variables take the form of update inputs in order to be updated or read by a network management tool.  Each Configuration 
Network  Variable  will  have  its  own  Map  Descriptor.    Since  the  data  carried  by  a  Network  Variable  is  intended  as  a 
configuration property for other already declared non-configuration Network Variable(s), no Data Array needs to be assigned 
to its Map Descriptor.  
Configuration  Properties  can  be  declared  to  belong  to  the  entire  Node,  to  an  Object(s)  or  to  a  Network  Variable(s).    This 
declaration defines the scope of the Configuration Property. Configuration Properties that belong to an Object are declared 
as  a  part  of  the  Object;  Configuration  Properties  associated  with  a  Network  Variable(s)  are  declared  as  belonging  to  the 
Network Variable(s) etc.  
A  Configuration  Property’s  Type  and  Responsible  Map  Descriptor(s)  are  declared  by  the  Configuration  Network  Variable’s 
self-documentation string as follows: 
For linking to the entire node:  
“&0,,0\x80,*SCPT Index+” 
Example: “&0,,0\x80,20” 
 
For linking to object(s):  
“&1,[Object Index(s)],0\x80,*SCPT Index+” 
Example: “&1,0.2.3,0\x80,23” 
 
For linking to network variable(s):  
“&2,*NV Index(s)+,0\x80,*SCPT Index+” 
Example: “&2,0.1.2.4.7,0\x80,20” 
 
Examples of configuration network variables are presented in Section 6.3.6  
Appendix A.6. LonMark Object Creation 
For  more  information  on  filling  out  the  Node  Self-Documentation  String  as  well  as  the  relevant  Network  Variable  Self-
Documentation Strings in order to create a LonMark Object please consult the following  documentation from the LonMark 
Interoperability Association a
 
Understanding LonMark Self-Documentation 
 
LonMark Application Layer Interoperability Guidelines 
The two examples given below will show how LonMark Objects can be assigned in FieldServer configuration files: 
The first example uses the standard Open Loop Sensor Object (Type 1) to create a Water Temperature Sensor that will send 
out its current status via Network Variable Updates. 
A typical recipient of these updates is given by example #2 which uses the LonMark Open Loop Actuator Object (Type 3) to 
create a  Water Heating Element  object  that will interpret the Network Variable it  receives and adjust  power to its heating 
element accordingly.