Appendix A.7. Node Status Operation 
When binding network variables on the FieldServer, the node status will be on-line before binding as well as after 
un-binding network variables.  A Node will go off-line only when a bound network variable of that node goes off-
line (e.g. is disconnected). 
When  using  a  network  tool  to  commission  the  FieldServer  (implicit  addressing),  the  FieldServer  LonWorks  Node 
must be placed ONLINE on the LonWorks network before it will pass data with other bound network variables.  The 
following messages may appear on the driver screen when using Ruinet which indicates that the FieldServer has 
not been put into the ONLINE state yet: 
"Not sending NV msg for [variable name], Node OFFLINE!"  
To set the FieldServer to ONLINE using LonMaker: 
 
Right-click on the FieldServer device and select Manage.  
 
On the Devices Tab, click the ONLINE button. 
 
The FieldServer LonWorks Node is always ONLINE when using explicit addressing. 
Note:  The  FieldServer  Node_Status  function  (refer  to  the  Bridge  Configuration  Manual)  looks  at  the  Node_ID 
configured  in  order  to  monitor  Node  status.    In  implicit  applications  this  may  not  be  the  real  Node_ID  since 
Node_ID is allocated by the network manager. 
Appendix A.8. Working with Binary Data 
When sending binary data on a LonWorks network, there are two SNVT’s that are most commonly used, namely 
SNVT_State and SNVT_Switch. 
SNVT_State is a 16 bit integer that allows the user to send 16 data bits to the remote device.  To do this, the 16 
data bits need to be packed into an integer word.  If this packing is already done when the value is transferred into 
the  FieldServer,  then  the  SNVT  need  only  be  linked  to  the  relevant  Data  Array  offset  for  transfer  out  of  the 
FieldServer.  However, if the FieldServer is picking up 16 separate bits from another network for this variable, then 
the FieldServer Packed_Bit function can be used to achieve the packing.  See the FieldServer Configuration manual 
for more details on the Packed_Bit function. 
SNVT_Switch is a two byte value consisting of an analog value in the left hand byte (VALUE portion), and a binary 
state in the right hand byte (STATE portion).  LonMark guidelines for this SNVT stipulate that the VALUE portion 
has a range from 0-100%, and that the STATE portion can assume a value of 1 or 0.  However, since the raw data 
type for these two  values is  byte (a value ranging  from 0-255), care needs to be taken when transferring  values 
into this SNVT to make sure  the source  values are within  the legal range.  If a  value  is placed into one of these 
bytes that is deemed out of range, then a -1 value will be sent on the LonWorks network to indicate out of range.  
Also  note  that  when  sending  binary  status  in  a  SNVT  Switch,  some  devices  expect  the  VALUE  portion  to  change 
when  the  STATUS  portion  changes,  so  an  analog  value  that  changes  in  sympathy  with  the  binary  state  may  be 
necessary.