April 1997
Maintenance Object Repair Procedures
Page 10-322
CO-DS1 (DS1 CO Trunk)
10
DS1 CO Dial Tone Seizure Test (#314)
DS1CO Dial Tone Seizure Test checks the trunk’s signaling capability provided
by the DS1 Interface circuit pack. The maintenance software initiates the test by
sending a "seizure" message to the DS1 Interface circuit pack and expects an
"active" reply from the DS1 interface circuit pack. If the "active" message is
received, then the test passes. If no message is received and the timer expires,
the test is aborted. If the DS1 Interface circuit pack sends a "reorder" message
back to maintenance software, then the test fails.
by the DS1 Interface circuit pack. The maintenance software initiates the test by
sending a "seizure" message to the DS1 Interface circuit pack and expects an
"active" reply from the DS1 interface circuit pack. If the "active" message is
received, then the test passes. If no message is received and the timer expires,
the test is aborted. If the DS1 Interface circuit pack sends a "reorder" message
back to maintenance software, then the test fails.
The test
CANNOT
be run on a trunk if one of the following cases is true:
0
NO
BOARD
BOARD
The test could not relate the internal ID to the port (no
board). This result could be due to incorrect
translations, no board is inserted, an incorrect board is
inserted, an insane board is inserted, or the board is
hyperactive (see note below).
board). This result could be due to incorrect
translations, no board is inserted, an incorrect board is
inserted, an insane board is inserted, or the board is
hyperactive (see note below).
1. Check to ensure that the board translations are
correct. Use the
list config
command, and resolve
any problems that are found.
2. If the board was found to be correctly inserted in
step 1, issue the
busyout board
command.
3. Issue the
reset board
command.
4. Issue the
release busy board
command.
5. Issue the
test board long
command.
This should re-establish the linkage between the internal
ID and the port. If this is not the case, dispatch to check
to ensure that there is a valid board inserted.
ID and the port. If this is not the case, dispatch to check
to ensure that there is a valid board inserted.
Hyperactivity causes some special problems with the
sequence suggested above. If the ports are translated
after issuing the
sequence suggested above. If the ports are translated
after issuing the
list config
command but the 'Vintage'
field reports that there is no board (when there really is a
board), then the
board), then the
busyout board
and the
release busy
board
commands will not work (even though the
reset
board
command will work). The software will put the
hyperactive board back in service after the hyperactivity
clears.
clears.
Table 10-90.
TEST #36 Port Audit and Update Test —
Continued
Error
Code
Test
Result
Description/ Recommendation
Continued on next page