5-2 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Set Up the Hardware
In this example, a ControlLogix chassis contains the Logix 5555
controller in slot 1 and a 1756-ENBT bridge module in slot 3. We
mounted the 1734-AENT adapter on a DIN rail in slot 0, with a
1734-OW2/C relay output module in slot 1, a 1734-OV4E/C sink
output module in slot 2, and a power supply (not shown).
controller in slot 1 and a 1756-ENBT bridge module in slot 3. We
mounted the 1734-AENT adapter on a DIN rail in slot 0, with a
1734-OW2/C relay output module in slot 1, a 1734-OV4E/C sink
output module in slot 2, and a power supply (not shown).
To work along with this example, set up your system as shown in the
figure.
figure.
• Note that in the example application, the Logix5555 controller
and 1756-ENBT module (firmware revision 2.3 or later) we
assume are in the slots shown in the figure.
assume are in the slots shown in the figure.
• Verify the IP addresses for your programming terminal,
1756-ENBT module, and 1734-AENT adapter.
• Verify the position (slot) of the I/O modules on the DIN rail.
• Verify that you properly connected all wiring and cabling.
• Be sure you configured your communication driver (such as
AB_ETH-1 or AB-ETHIP-1) in RSLinx software as described in
the Configure the RSLinx Ethernet Communication Driver
appendix of this manual.
the Configure the RSLinx Ethernet Communication Driver
appendix of this manual.
Local
Chassis
Chassis
POINT I/O
Logix5555
Controller (slot 1)
Controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
10.88.70.4 (slot 3)
Data
Switch
10.88.70.26
Programming
Terminal
Terminal
Slot 0 1 2 3
1734-AENT
10.88.70.2
10.88.70.2
Slot 0 1 2 3 4
31393-M