Omron CJ1W-EIP21 用户手册

下载
页码 464
88
Auxiliary Area Data
Section 4-5
4-5
Auxiliary Area Data
The following table and descriptions cover the words and bits in the CPU
Unit’s Auxiliary Area that are related to the EtherNet/IP Unit.
4-5-1
Read-only Bits/Words
Word(s)
Bit(s)
Name
Function
Settings
A202
A20200 to 
A20207
Communications 
Port Enabled Flags
Bits A20200 to A20207 turn ON when a network 
instruction (SEND, RECV, CMND, or PMCR) can be 
executed with the corresponding port number. Bits 
00 to 07 correspond to communications ports 0 to 7.
0: Network communi-
cations running
1: No network com-
munications running
A203 to 
A210
---
Communications 
Port Completion 
Codes
These words contain the completion codes for the 
corresponding port numbers when network 
instructions (SEND, RECV, CMND, or PMCR) have 
been executed. Words A203 to A210 correspond to 
communications ports 0 to 7.
0000: No error
Not 0000: Error code
A219
A21900 to 
A21907
Communications 
Port Error Flags
Bits A21900 to A21907 turn ON when an error 
occurred during execution of a network instruction 
(SEND, RECV, CMND, or PMCR). Bits 00 to 07 
correspond to communications ports 0 to 7.
0: Normal end
1: Error end
A302
A30200 to 
A30215
CPU Bus Unit 
Initializing Flags
Bits A30200 through A30215 turn ON while the 
corresponding CPU Bus Units (Units #0 through 
#15, respectively) are initializing. The bits will turn 
ON either when power is turned ON or when a CPU 
Bus Unit Restart Bit (A50100 to A50115) is turned 
ON.
0: Not initializing
1: Initializing (System 
will automatically turn 
the flag OFF when ini-
tialization has been 
completed.)
A402
A40203
CPU Bus Unit Set-
ting Error Flag 
(Non-fatal error)
Bit A40203 is turned ON when the CPU Bus Units 
actually installed differ from the Units registered in 
the I/O tables. The ERR/ALM indicator on the front 
of the CPU Unit will flash, but CPU operation will 
continue.
The unit number of the CPU Bus Unit involved is 
stored in word A427.
0: No setting error
1: Setting error
A40207
CPU Bus Unit Error 
Flag 
(Non-fatal error)
Bit A40207 is turned ON when an error occurs 
during the transmission of data between the CPU 
and CPU Bus Units. The ERR/ALM indicator on the 
front of the CPU Unit will flash, but CPU operation 
will continue. The Unit where the error occurred will 
stop.
The unit number of the CPU Bus Unit involved is 
stored in word A422.
0: No unit number 
error
1: Unit number error
A403
A40300 to 
A40308
Memory Error 
Location
When a memory error occurs, the Memory Error 
Flag (A40115) is turned ON and one of the following 
flags is turned ON to indicate the memory area 
where the error occurred.
A40300: User program
A40304: PLC Setup
A40305: Registered I/O Tables
A40307: Routing Tables
The ERR/ALM indicator on the front of the CPU Unit 
will light and CPU operation will stop.
0: Normal
1: Error
A410
A41000 to 
A41015
CPU Bus Unit Num-
ber Duplication 
Flags
The Duplication Error Flag (A40113) and the 
corresponding flag in A410 will be turned ON when 
a CPU Bus Unit’s unit number has been 
duplicated. Bits 00 to 15 correspond to unit numbers 
0 to F. 
The ERR/ALM indicator on the front of the CPU Unit 
will light and CPU operation will stop.
0: No duplication
1: Duplication