Auxiliary Area Data
Section 4-5
4-5-2
Read/Write Bits (User Settings)
A417
A41700 to 
A41715
CPU Bus Unit Error, 
Unit Number Flags
When an error occurs in a data exchange between 
the CPU Unit and a CPU Bus Unit, the CPU Bus 
Unit Error Flag (A40207) and the corresponding flag 
in A417 are turned ON. Bits 00 to 15 correspond to 
unit numbers 0 to F. 
The ERR/ALM indicator on the front of the CPU Unit 
will flash, but CPU operation will continue.
0: No error
1: Error
A427
A42700 to 
A42715
CPU Bus Unit Set-
ting Error, Unit 
Number Flags
When a CPU Bus Unit Setting Error occurs, A40203 
and the corresponding flag in A27 are turned ON. 
Bits 00 to 15 correspond to unit numbers 0 to F.
The ERR/ALM indicator on the front of the CPU Unit 
will flash, but CPU operation will continue.
0: No setting error
1: Setting error
Word
Bits
Name
Description
Settings
A501
A50100 to 
A50115
CPU Bus Unit 
Restart Bits
Bits A50100 through A50115 can be turned ON to 
reset CPU Bus Units number #0 through #15, 
respectively. 
Note The CPU Bus Unit Initializing Flags (A30200 
to A30215) will turn ON when initialization of 
the Units begins and turn OFF when it is com-
pleted.
Note When turning ON the CPU Bus Unit Restart 
Bit from a ladder program, use the SET 
instruction. 
OFF to ON: 
Unit restarted.
Automatically turned 
OFF by system after 
restart processing 
has been completed.
Word(s)
Bit(s)
Name
Function
Settings